4-20 mA Output Connections

The Innova-Flo meter has a single 4-20 mA loop. The 4-20 mA loop current
is controlled by the meter electronics. The electronics must be wired in series
with the sense resistor or current meter. The current control electronics re-
quire 12 volts at the input terminals to operate correctly.

The maximum loop resistance (load) for the current loop output is depend-
ent upon the supply voltage and is given in Figure 2-16. The 4-20 mA loop
is optically isolated from the flow meter electronics.

R

load

is the total resistance in the loop, including the wiring resistance (R

load

=

R

wire

+ R

sense

). To calculate R

max

, the maximum R

load

for the loop, use the

maximum loop current, 20 mA. The voltage drop in the loop due to resis-
tance is 20 mA times R

load

and this drop is subtracted from the input voltage.

Thus:

The maximum resistance R

load

= R

max

= 50 * (V

supply

– 12V).