Chapter 3 Operation

Series 220/221 Instruction Manual

Output Menu


Password

ENTER

Use
keys to access menus

Output

Menu

4-20mA Output 1

More >

ENTER

Run Mode

< Measure >

None
Mass

Volume

< 4mA = xxxx >

xxxx

< 20mA = xxxx >

xxxx

< TimeConst (sec)

xxxx

Example for Setting an Output

The following shows how to set Output 1 to measure volumetric flow with 4 mA = 0 gal/min and 20 mA = 100
gal/min with a time constant of 5 seconds. (All outputs are disabled while using the Setup Menus.)

First, set the desired units of measurement:

1. Use ÕÖ keys to move to the Units Menu (see page 3-8).
2. Press Ø key until Volume Flow Unit appears. Press

ENTER

.

3. Press Ø key until gal appears in the numerator. Press Ö key to move the underline cursor to the

denominator. Press the Ø key until min appears in the denominator. Press

ENTER

to select.

4. Press × key until Units Menu appears.

Second, set the analog output:

1. Use ÕÖ keys to move to the Output Menu.
2. Press the Ø key until 4-20mA Output 1 appears.
3. Press Ö key to access Measure selections. Press

ENTER

and press the Ø key to select Volume. Press

ENTER

.

4. Press Ö key to set the 4 mA point in the units you have selected for volume of gal/min. Press

ENTER

and use ЧШХЦ keys to set 0 or 0.0. Press

ENTER

.

5. Press Ö key to set the 20 mA point. Press

ENTER

and use ЧШХЦ keys to set 100 or 100.0. Press

ENTER

.

6. Press Ö key to select the Time Constant. Press

ENTER

and use ЧШХЦ keys to select 5. Press

ENTER

.

7. Press the

EXIT

key and answer

YES

to permanently save your changes.

3-4

IM-22