Series 220/221 Instruction Manual

Chapter 4 HART Communications

Fast Key Sequence

Use password 16363.

Sequence Description

Access

Notes

1,1,1

Snsr

View

Primary variable value

1,1,2

AI % Rnge

View

Analog output % range

1,1,3

AO1

View

Analog output, mA

1,2,1

Test Device

N/A

Not used

1,2,2,1

4 mA

View

Loop test, fix analog output at 4 mA

1,2,2,2

20 mA

View

Loop test, fix analog output at 20 mA

1,2,2,3

Other

Edit

Loop test, fix analog output at mA value entered

1,2,2,4

End

Exit loop test

1,2,3,1,1 4

mA

N/A Not used, apply values

1,2,3,1,2 20

mA

N/A Not used, apply values

1,2,3,1,3 Exit

Exit apply values

1,2,3,2,1 PV

LRV

Edit Primary variable lower range value

1,2,3,2,2 PV

URV

Edit Primary variable upper range value

1,2,3,2,3 PV

USL

View

Primary variable upper sensor limit

1,2,3,2,4 PV

LSL

View

Primary

variable lower sensor limit

1,2,4 D/A

Trim Edit

Calibrate electronics 4mA and 20mAvalues

1,3,1 Tag

Edit

Tag

1,3,2

PV unit

Edit

Primary variable units

1,3,3,1 PV

LRV

Edit

Primary variable lower range value

1,3,3,2 PV

URV

Edit

Primary variable upper range value

1,3,3,3 PV

LSL

View

Primary

variable upper sensor limit

1,3,3,4 PV

USL

View

Primary

variable lower sensor limit

1,3,4,1 Distributor

N/A

Not

used

1,3,4,2 Model

N/A

Not

used

1,3,4,3 Dev

id

View

Device identification

1,3,4,4 Tag

Edit

Tag

1,3,4,5 Date

Edit

Date

1,3,4,6 Write

Protect View Write

protect

1,3,4,7 Descriptor

Edit Vortex

flowmeter

1,3,4,8 Message

Edit

32

character alphanumeric message

1,3,4,9

PV snsr s/n

View

Primary variable sensor serial number

1,3,4,menu

Final assy #

Edit

Final assembly number

1,3,4,menu,1 Universal

Rev

View Universal

revision

1,3,4,menu,2

Fld dev Rev

View

Field device revision

1,3,4,menu,3

Software Rev

View

Software revision

1,3,5

PV Xfer fnctn

View

Linear

1,3,6

PV Damp

Edit

Primary variable damping (time constant) in seconds

1,4,1,1

PV

View

Primary variable value

1,4,1,2

PV Sensor Unit

Edit

Primary variable units

1,4,1,3 Sensor

Information

View

PV LSL, PV USL, PV Min span

1,4,2,1

Snsr Damp

Edit

Primary variable damping (time constant) in seconds

1,4,2,2,1 PV

LRV

Edit Primary variable low range value

1,4,2,2,2 PV

URV

Edit Primary variable upper range value

1,4,2,3,1 PV

LRV

Edit Primary variable low range value

1,4,2,3,2 PV

URV

Edit Primary variable upper range value

1,4,2,4 Xfer

Fnctn View

Linear

1,4,2,5

AI % rnge

View

Analog output % range

1,4,3,1,1 AO1

View

Analog output, mA

1,4,3,1,2

AO alarm typ

N/A

Not used



Continued on next page

IM-22

4-3