Chapter 3 Operation

Series 220/221 Instruction Manual

Totalizer Menu

Password

ENTER

Use
keys to access menus

Totalizer

Menu

Totaling

Inactive

Mass

Volume

ENTER

Run Mode

(unit)/Pulse

xxxx

Reset Total?

YES or NO

Example:

Maximum flowrate = 600 gallons per minute
(600 gallons per minute = 10 gallons per second)

If unit per pulse is set to 600 gallons per pulse,
the totalizer will pulse once every minute.

If unit per pulse is set to 10 gallons per pulse,
the totalizer will pulse once every second.

Use the Totalizer Menu to configure and monitor the totalizer. The totalizer output is a 50
millisecond (.05 second) positive pulse (relay closed for 50 milliseconds). The totalizer
cannot operate faster than one pulse every 100 millisecond (.1 second). A good rule to follow
is to set the unit per pulse value equal to the maximum flow in the same units per second.
This will limit the pulse to no faster than one pulse every second.

Example for Setting the Totalizer

The following shows how to set the totalizer to track volumetric total gallons. (All outputs are disabled
while using the Setup Menus.)

First, set the desired units of measurement:

1. Use ÕÖ keys to move to the Units Menu (see to page 3-8).
2. Press Ø key until Volume Flow Unit appears. Press

ENTER

.

3. Press Ø key until gal appears in the numerator. Press Ö key to move the underline cursor to the

denominator. Press the Ø key until min appears in the denominator. Press

ENTER

to select.

4. Press × key until Units Menu appears.

Second, set the pulse output:

1. Use ÕÖ keys to move to the Totalizer Menu.
2. Press the Ø key until Totaling appears.
3. Press

ENTER

and press the Ø key to select Volume. Press

ENTER

.

4. Press Ø key to set the gallons per pulse. Press

ENTER

and use ЧШХЦ keys to set the pulse

value equal to the maximum flow in the same units per second. This will limit the frequency to
1 Hz. Press

ENTER

.

5. To reset the totalizer, press Ø key until Reset Total? appears. Press

ENTER

and the Ø key to reset

the totalizer if desired. Press

ENTER.

6. Press the

EXIT

key and answer

YES

to permanently save your changes.

3-6

IM-22