Warning!

Agency approval for hazardous location installations varies between flow meter models.
Consult the factory for specific flow meter approvals before any hazardous location instal-
lation. For explosion proof installations, you must use solid metal conduit and follow
NFPA (or your local code) approved wiring methods.

Hot tapping must be performed by a trained professional. U.S. regulations often require a
hot tap permit. The manufacturer of the hot tap equipment and/or the contractor perform-
ing the hot tap is responsible for providing proof of such a permit.

All flow meter connections, isolation valves and fittings for cold/hot tapping must have the
same or higher pressure rating as the main pipeline.

For Series 221 insertion flow meter installations, an insertion tool must be used for any
installation where a flow meter is inserted under pressure greater than 50 psig.

To avoid serious injury, DO NOT loosen a compression fitting under pressure.

All wiring procedures must be performed with the power Off.

Before attempting any flow meter repair, verify that the line is de-pressurized.

Always remove main power before disassembling any part of the mass flow meter.

Caution!

Calibration must be performed by qualified personnel. Sierra Instruments, Inc., strongly rec-
ommends that you return your flow meter to the factory for calibration.

In order to achieve accurate and repeatable performance, the flow meter must be in-
stalled with the specified minimum length of straight pipe upstream and downstream of
the flow meter’s sensor head.

When using toxic or corrosive gases, purge the line with inert gas for a minimum of four
hours at full gas flow before installing the flow meter.

Wafer-style flow meter gaskets must be carefully aligned to ensure accurate flow meas-
urement.

For Series 221 insertion flow meter installations, the sensor alignment pointer must point
downstream in the direction of flow.