Lennox Hearth ELITE ELDV-40NM User Manual

Page 18

Advertising
background image

18

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Support

Brackets

Building

Support

Framing

SV4.5E90

Elbow

Ceiling

Fireplace

SV4.5L6/12/24/36/48

Vent Sections

Vertical

Rise

Support Bracket Spacing

Every 5 ft (1.52 m)

TYPICAL HORIZONTAL VENT INSTALLATION

u

When Using Secure Flex™,

Use Firestop / Spacer SF4.5VF

u

Firestop / Spacer

SV4.5VF

Figure 28

Typical

Termination

Shown

Typical

Termination

Shown

Exterior

Wall

Horizontal / Inclined Run

See Figure 20 on Page 14 for vertical

vent section support.

Push the vent component against the previous

section until it fully engages, then twist the

component clockwise running the dimples down

and along the incline channels until they seat at

the end of the channels. This seating position

is indicated by the alignment of the arrow and

dimple as shown in Figure 19 on Page 14.

F. Install firestop/spacer at ceiling -

When using Secure Vent, use SV4.5VF firestop/

spacer at ceiling joists; when using Secure Flex,

use SF4.5VF firestop/spacer. If there is living

space above the ceiling level, the firestop/spacer

must be installed on the bottom side of the

ceiling. If attic space is above the ceiling, the

firestop/spacer must be installed on the top side

of the joist. Route the vent sections through the

framed opening and secure the firestop/spacer

with 8d nails or other appropriate fasteners at

each corner.

Remember to maintain 1" (25 mm) clearance

to combustibles, framing members, and attic

or ceiling insulation when running vertical

chimney sections.

G. Support the vertical run sections -

See Section E on Page 14.

H. Change vent direction - At transition from or

to a horizontal/inclined run, install the SV4.5E45

and SV4.5E90 elbows in the same manner as

the straight vent sections.

The elbows feature a twist section to allow

them to be routed about the center axis of their

initial collar section to align with the required

direction of the next vent run element. Twist

elbow sections in a clockwise direction only

so as to avoid the possibility of unlocking any

of the previously connected vent sections (see

Figure 19 on Page 14).

I. Continue installation of horizontal/inclined

sections - Continue with the installation of the

straight vent sections in horizontal/inclined run

as described in Step E. Install support straps

every 5 ft. (1.52 m) along horizontal/inclined vent

runs using conventional plumber’s tape.

See Figure 28. It is very important that the

horizontal/inclined run be maintained in a

straight (no dips) and recommended to be in

a slightly elevated plane, in a direction away

from the fireplace of 1/4" rise per foot (20 mm

per meter) which is ideal, though rise per foot

run ratios that are smaller are acceptable all the

way down to at or near level.

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides

for all vertical runs; and 3" (76 mm) at the top,

1" (25 mm) at sides, and 1" (25 mm) at the

bottom for all horizontal/inclined runs.

Use a carpenters level to measure from a

constant surface and adjust the support straps

as necessary.

D. Attach vent components to appliance - To

attach a vent component to the appliance collar,

align the dimpled end over the collar, adjusting the

radial alignment until the four locking dimples are

aligned with the inlets of the four incline channels

on the collar (see Figure 19 on Page 14).

Push the vent component against the collar

until it fully engages, then twist the component

clockwise, running the dimples down and along

the incline channels until they seat at the end of

the channels. The unitized design of the Secure

Vent™ components will engage and seal both

the inner and outer pipe elements with the same

procedure. Sealant and securing screws are

not required.

Note: An elbow may not be directly attached

to the appliance collar.

E. Attach vent components to each other - Other

vent sections may be added to the previously

installed section in accordance with the require-

ments of the vent tables. To add another vent

component to a length of vent run, align the

dimpled end of the component over the inclined

channel end of the previously installed section,

adjusting the radial alignment until the four lock-

ing dimples are aligned with the inlets of the four

incline channels of the previous section.

Advertising