Side elevation view – Lennox Hearth ELITE ELDV-40NM User Manual

Page 6

Advertising
background image

6

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

12

X

Roof Pitch is X/12

2 FT

MIN.

2 FT MIN.

Lowest

Discharge

Opening

H*

*H = MINIMUM HEIGHT FROM ROOF TO

LOWEST DISCHARGE OPENING OF VENT

TERMINATION HEIGHTS FOR VENTS ABOVE

FLAT OR SLOPED ROOFS

Horizontal Overhang

Vertical

Wall

Vent

Termination

Storm Collar

Concentric

Vent Pipe

Flashing

1 inch (25.4 mm) Minimum

Clearance to Combustibles

Figure 5

Vertical Vent Termination Clearances

VENT TERMINATION CLEARANCES

These instructions should be used as a

guideline and do not supersede local codes

in any way. Install venting according to local

codes, these instructions, the current National

Fuel Gas Code (ANSI-Z223.1) in the USA or

the current standards of CAN/CSA-B149.1

in Canada.

Vertical Vent Termination Clearances

Terminate multiple vent terminations according

to the installation codes listed above. Also see

Figure 4.

Terminate single vent caps relative to building

components according to Figure 5.

Note - See Figure 30 on Page 19 for the exterior wall recess

allowances of the square horizontal termination.

Termination Heights For Vents

Above Flat Or Sloped Roofs

Ref. NFPA 54 / ANSI Z223.1

Roof Pitch

* Feet

* Meters

Flat to 6/12

1.0

0.3

6/12 to 7/12

1.25

0.38

7/12 to 8/12

1.5

0.46

8/12 to 9/12

2.0

0.61

9/12 to 10/12

2.5

0.76

10/12 to 11/12

3.25

0.99

11/12 to 12/12

4.0

1.22

12/12 to 14/12

5.0

1.52

14/12 to 16/12

6.0

1.83

16/12 to 18/12

7.0

2.13

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8.0

2.44

The vent / air intake termination clearances

above the high side of an angled roof is as

shown in the following chart:

Figure 6

6"

(152 mm)

12"

(305 mm)

Combustible Projection greater

Horizontal Vent Termination Clearances

Combustible Projection

2-1/2 inches or less in length

18"

(457 mm)

Ventilated

Soffit

Unventilated

Soffit

than 2-1/2 inches in length

Termination Kit

Side Elevation View

Termination Kit

All horizontal terminations

may be located as close as

6” (152mm) to any

(non-combustible and

combustible) exterior

sidewall. This distance

may be decreased to 2”

(51mm) for non--

combustible exterior

sidewalls only, if the

SV4.5HT-2 termination

is used.

Horizontal Vent Termination Clearances

The horizontal vent termination must have a minimum of 6" (152 mm) clearance to any overhead

combustible projection of 2-1/2" (64 mm) or less (see Figure 6). For projections exceeding 2-1/2"

(64 mm), see Figure 6. For additional vent location restrictions refer to Figure 7 on Page 7.

12”

(305mm)

Minimum

Figure 4 - Multiple Terminations

Be aware that this is a heat producing ap-

pliance. Objects placed above the unit are

exposed to elevated temperatures.

Do not insulate the space between the appli-

ance and the area above it (see Figure 8 ).

The minimum height from the base of the appli-

ance to the underside of combustible materials

used to construct a utility shelf in this fashion

is shown in Figure 8.

The appliance should be mounted on a fully

supported base extending the full width and

depth of the unit. The appliance may be located

on or near conventional construction materials.

However, if installed on combustible materials,

such as carpeting, vinyl tile, etc., a metal or

wood barrier covering the entire bottom surface

must be used.