Lennox Hearth ELITE ELDV-40NM User Manual

Page 39

Advertising
background image

39

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 55

Millivolt Appliances

Step 5. SIT Systems - Refer to Figure 56 and

the instructions provided with the kit. Using

a Torx T20 (with 1/4" shank and center hole),

remove and discard the three pressure regulator

mounting screws. Remove the pressure regu-

lator, spring, poppet, diaphragm and bushing.

Discard all removed components.

Ensure the rubber gasket installed on the

back of the replacement pressure regulator is

properly positioned Tighten screws to 25 In.

lb. torque.

Electronic Appliances

Step 7. Dexen Electronic Valves - See Figure

58 and the instructions provided with the kit.

Remove and discard the two pressure regula-

tor mounting screws. Remove the pressure

regulator and diaphragm. Discard all removed

components. Ensure the provided diaphragm

is installed properly onto the replacement

pressure regulator and install the new pres-

sure regulator using the new screws supplied

with the kit. Tighten screws.

Step 5. Attach manometer to the manifold side

pressure test fitting and verify manifold pressure

reads 3.5 inches water column (0.87 kPa) for

natural gas, and 10.0 inches water column (2.49

kPa) for propane gas.

Step 6. See Figure 57 and remove the pilot

hood assembly to access the hexed pilot orifice.

Remove and replace the orifice with the one

provided with the kit.

Figure 56

Figure 57

Pressure

Regulator

Remove

These

Components

Pilot
Orifice

Figure 58

- Dexen Electronic Gas Valve

Supply Gas

Inlet

Pressure-Tap

(Manifold)

Regulator

Mounting

Screw

Burner Stage

Terminal

Gas

Outlet

To Burner

Ground (TP)

Pilot Stage

Terminal

Pilot Gas Outlet

Pressure-Tap

(Inlet)

PILOT

OUT

VENT

LO

TH TP

TH

TP

HI

IN

IN

Note: If the igniter is damaged, a replace-

ment kit is available, order Catalog Number

87L54.

Step 10. Attach the conversion label provided

in the conversion kit next to the rating plate on

the appliance.

Step 11. Turn on gas supply and test for gas

leaks (refer to page 26).

Always test pressure with the valve regulator

control at the highest setting.

See Figure 59 and replace the pilot orifice as

follows: Remove pilot hood assembly to access

the phillipped pilot orifice. Remove and replace

the orifice with the one provided with the kit.

Exercise extreme care to prevent damage to

or breakage of the igniter assembly.

All Models

Note: Use pipe joint compound or Teflon tape

on all pipe fittings before installing (ensure

propane resistant compounds are used in

propane applications, do not use pipe joint

compounds on flare fittings).

Step 8. (Refer to Figure 55)

A. Remove the orifice from the manifold and

replace it with the one provided in the kit. See

Table 9 for orifice sizes for natural and pro-

pane models. Figure 60 illustrates the orifice.

Always check and verify orifice size.

B. Retrieve the burner and slide the venturi

tube over the orifice. Set the shutter adjusting

opening as shown in Figure 53, Page 34.

Step 9. Reassemble the remaining components

by reversing the procedures outlined in the

preceding steps.

Figure 59

Figure 60

ELECTRONIC

Pilot

Hood

Sensor

Igniter

Burner Orifice Sizes

Elevation 0-4500 feet ( 0-1372 meters)

Model

Series

Nat.Gas

drill size (inches)

Propane

drill size (inches)

ELDV35

#38 (0.1015")*

99K76•

#53 (0.0595")*

39L10•

ELDV40

#37 (0.1040")*

24M10•

(0.062")*

21L01•

ELDV45

#36 (0.1065")*

74L88•

#52 (0.0635")*

80L41•

Table 9

* Standard size installed at factory

• Part /Cat. Number