NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

D. Install Firestop / Spacers at ceilings and walls -

When Secure Flex penetrates a wall or ceiling,

a firestop / spacer is required: use the SF4.5 VF

firestop / spacer for ceilings and the SF4.5 HF

firestop / spacer for walls. See the appropriate

sections and Figures shown throughout the vent-

ing section for their installation requirements.

APPLY ONLY MIL-PAC BLACK

HIGH TEMPERATURE SEALANT

(Cat. No. 10K81) to the outside

surface of both collars of the

adaptor (be especially careful to

fill the grooves of the outer collar

to be covered by the flexible pipe)

and slide flexible pipe over inner

and outer adaptor collars.

1 3/4 inch (44 mm) Flexible

Pipe and Adaptor Outer Collar

Overlap

Adaptor (SV4.5RF)

Attach Adaptor to Appliance

Collar, or Secure Vent Sections

Flex Vent

Gear Clamps

Securing Screw - 3

Places, 120° apart

(equally spaced) Just

Below Gear Clamp

1 3/4 in. (44 mm) Flexible

Pipe and Adaptor Inner Collar

Overlap

Securing Screw - 3 Places

Equidistant (equally spaced)

Just Below Gear Clamp)

VERTICAL OR HORIZONTAL VENTING USING

SECuRE FLEx™

KITS AND COMPONENTS

Secure Flex™ venting kits and components may

be used in any venting application in place of rigid

Secure Vent™ (SV4.5) direct-vent components.

All restrictions, clearances and allowances that

pertain to the rigid piping apply to the flexible

venting. Secure Flex kits may not be modified;

also, under no circumstances may separate

sections of flex pipe be joined together.

Using adaptor (SV4.5RF), Secure Flex kits

may be added to the end of a vent run made

up of rigid Secure Vent (SV4.5) vent sections

provided that doing so does not violate any of

the venting length, height, routing, horizontal

to vertical ratio requirements or clearance

considerations detailed in this manual.

Secure Flex kits come with an adaptor that

can be fitted to the inclined channel end of

the last Secure Vent (SV4.5) vent section in a

rigid system in the exact same fashion as any

other Secure Vent section. Align the dimpled

end of the adaptor over the previously installed

section or appliance collar, adjusting the radial

alignment until the four locking dimples of the

adaptor are aligned with the inlets of the four

incline channels of the last vent section or collar.

Push on the adaptor until it fully engages, then

twist the adaptor clockwise running the dimples

down and along the incline channels until they

seat at the end of the channels.

Attach the flexible vent to the adaptor as fol-

lows (see also Figure 34):

A. Install the Inner Flex Pipe -

1. Install the small gear clamp loosely around

the inner flexible vent pipe, push it back out

of the way.

2. Apply a bead of Mill-Pac Black (700° F) high

temperature sealant - Catalog No. 10K81

to the inner adaptor collar, approximately

1/2 inch from the end.

3. Pull and extend the inner flexible vent pipe.

4. Slide the inner flex pipe over the adaptor col-

lar. Ensure the flexible vent pipe completely

engages the adaptor collar to a distance of

1 3/4 inches from the end, and that it is free

from damage or tears.

5. Slide the gear clamp down and tighten it

fully to secure the flexible vent to the adaptor

inner collar approximately 3/4 inch from the

end of the flex.

6. Install three screws, 120 degrees apart,

through the flexible vent pipe and into the

adaptor collar just below the gear clamp to

provide additional security to the connec-

tion.

B. Install the Outer Flex Pipe -

1. Install the large gear clamp loosely around

the outer flexible vent pipe, push it back out

of the way.

2. Apply a bead of Mill-Pac Black (700° F) high

temperature sealant - Catalog No. 10K81)

to the outer adaptor collar; to the grooves

of the collar which extend approximately 1

inch from the end and to the flat surface,

approximately 1-3/8 inches from the end.

3. Pull and extend outer flexible vent pipe.

4. Slide the outer flex pipe over the adaptor col-

lar. Ensure the flexible vent pipe completely

engages the adaptor collar to a distance of

1-3/8 inches from the end, and that it is free

from damage or tears.

5. Slide the gear clamp down and tighten it

fully to secure the flexible vent to the adaptor

outer collar approximately 3/4 inch from the

end of the flex.

6. Install three screws, 120 degrees apart,

through the flexible vent pipe and into the

adaptor collar just below the gear clamp to

provide additional security to the connec-

tion.

C. Route Flex Vent -

Ensure that the flex vent is properly routed to

provide the required clearance. Do not allow the

flexible vent to bend in a radius tighter than 5"

(127 mm). Refer to Figure 35. Space out the

internal flex vent spacers evenly - approximately

every 6 inches - and avoid kinking of inner pipe.

Support horizontal sections of flex with metal

straps at 2 foot (0.61 m) intervals.

E. Attach Flex Vent to Termination -

Secure Flex components can be purchased

separately and attached to bulk lengths of Se-

cure Flex flexible tubing cut to size at the job

site. Secure the flexible vent to the Secure Flex

terminations in the same manner (see Figure

34) as it was attached to the adaptor.

Note: Secure Flex vent must be attached to Se-

cure Flex terminations only. DO NOT substitute

Secure Vent terminations or the Secure Vent

adaptor for Secure Flex components. The col-

lars of Secure Flex terminations and adaptors

have a different diameter than that used with

the Secure Vent pipe. Additionally, Secure Flex

components have an extended length center

tube for use in attaching the flexible vent.

Figure 34

Flexible Vent

Section

5” (127 mm)

Radius

Minimum

Figure 35

Note: Outer Pipe Is Pulled Away To

Show The Detail of The Inner Pipe