Warning – Lennox Hearth ELITE ELDV-40NM User Manual

Page 20

Advertising
background image

20

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

See Table 9 as an aid in venting component selection

for a particular range of exterior wall thicknesses.

HORIZONTAL VENT FIGURES/TABLES

Notes:

• Secure Vent™ components (rigid vent pipe and terminal) are shown

in the Figures; Secure Flex™ components (flexible vent pipe and

terminal) may also be used.

Two 45 degree elbows may be used in place of one 90 degree elbow.

The same rise to run ratios, as shown in the venting Figures for 90

elbows, must be followed if 45 degree elbows are used.

SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be

used anytime vent pipe passes through a combustible floor or ceiling.

SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must

be used anytime vent pipe passes through a combustible wall.

• It is very important that the horizontal/inclined run be maintained

in a straight (no dips) and recommended to be in a slightly elevated

plane, in a direction away from the fireplace of 1/4" rise per foot (20

mm per meter) which is ideal, though rise per foot run ratios that are

smaller are acceptable all the way down to at or near level.

The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run

of 20 feet.

• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE.

Use Table 9 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

Figure 31

-

Top Vent - ONE 90 DEGREE ELBOW -

ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE

Typical termination shown.

Venting Components Required for Various Exterior Wall Thick-

nesses, when using Typical Termination Kits

Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only

6 to 9-1/4 (152 to 235)

Termination Kit and 6 In. Vent

Section (SV4.5L6)

10-3/4 to 14 (273 to 356)

Termination Kit and 12 in.

Vent Section (SV4.5L12)

16-3/4 to 20 (426 to 508)

Termination Kit and Tele-

scopic Section (SV4.5L12)

11-3/4 to 20 (299 to 508)

Table 9

Note: See Figure 30 showing wall thickness range

when using SV4.5HT-2 termination kit.

E

L

B

A

T

C

m

u

m

i

n

i

M

V

m

u

m

i

x

a

M

H

t

e

e

f

)

m

(

t

e

e

f

)

m

(

*

)

1

0

6

.

0

(

4

/

1

3

)

1

9

9

.

0

(

3

)

4

1

9

.

0

(

7

)

4

3

1

.

2

(

4

)

2

2

.

1

(

2

/

1

0

1

)

2

.

3

(

5

)

4

2

5

.

1

(

4

1

)

7

6

2

.

4

(

6

)

9

2

7

.

1

(

2

/

1

7

1

)

3

3

.

5

(

7

)

4

3

1

.

2

(

0

2

)

2

.

6

(

.

x

a

M

)

m

4

.

2

1

(

t

e

e

f

0

4

=

H

+

V

.

x

a

M

)

m

2

.

6

(

t

e

e

f

0

2

=

H

H

V

v

u

When using Secure Flex,

use Firestop/Spacer

SF4.5VF.

u

Ceiling

Firestop/Spacer

(SV4.5VF)

v

When using Secure Flex,

use Firestop/Spacer

SF4.5HF.

Wall Firestop/Spacer

(SV4.5HF)

Min. One

Foot Vent

Section

Required

Example: If 20 feet of (H) hori-

zontal vent run is needed, then

4 feet minimum of (V) vertical

vent will be required.

This table shows a 1(V) to

5(H) ratio. For every 1 foot of

vertical, you are allowed 5 feet

of (H) horizontal run up to a

maximum (H) horizontal run

of 20 feet.

WARNING

Under no circumstances, may separate sections of

concentric flexible vent pipe be joined together.

Advertising