Installation and Configuration

11

6.1.2 Installing the Adjustable Rack-Mount Kit—Sold Separately

This kit contains parts needed to mount several different models of UPS and external battery cabi-

nets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per

pair of adjustable rack-mounting brackets is 200 pounds (91 kg).
Parts included are:

Tools needed for installation are:

• one Phillips screwdriver
• one 7mm wrench

The adjustable rack-mounting brackets feature retaining latches to prevent users from inadvertently

sliding the UPS or battery cabinet out of the rack.
To install the rack mount brackets:
1. Unpack two (2) rack-mounting bracket assemblies and

mounting hardware from this kit. Bracket assemblies are

interchangeable between left-hand or right-hand.
Remove inner member of each bracket assembly as shown

in at right by extending it to its outermost position,

depressing the retaining latch and then pulling the inner

member out of the bracket assembly.

2. Determine the height position inside the rack enclosure

where you want to mount the UPS or battery cabinet.

3. Install the rear member of each bracket assembly into rack

enclosure with two (2) M5 screws provided in this kit (see

figure at right). The return flanges on the bracket assembly

fit to the inside of rack mounting rails. Insert screws loosely

(finger-tight) into the top and bottom holes of the return

flange on the rear member. Extend the bracket assembly by

sliding the front member forward until it touches the front

rack mounting rail. Insert two (2) M5 screws loosely (finger-

tight) into top and bottom holes of the return flange on each

front member. Make sure bracket assemblies are at the

same mounting height on all four (4) rack mounting rails.

Item

Quantity

Rear bracket members

2

Front bracket members

2

Inner bracket members

2

M4 x 8mm machine screws

16

M4 locking hex nuts

8

M5 x 16 mm machine screws

12

Grease packet.

1

!

CAUTION

Reduce the risk of tipping the rack enclosure by

placing the UPS or battery cabinet in the lowest

possible rack position.

Return

flanges

Inner

members

Front

members

Retaining

Latches

M5 screws

M5 screws

Front rack

mounting rails

Rear rack

mounting

rails