0 troubleshooting, Table 4 fault indicators, Roubleshooting – Liebert GXT2-6000 RT208 User Manual

Page 42: Table 4, Fault indicators

Advertising
background image

Troubleshooting

36

13.0 T

ROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the UPStation

GXT2-6000RT208 develops a problem. Use this information to determine whether external factors

caused the problem and how to remedy the situation.
1. The Fault indicator will illuminate, indicating the UPS has detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional Load Level/Battery Level indicators will be illuminated to provide a

diagnostic aid to the operator, as described below:

Under fault conditions, the Fault indicators will be illuminated indefinitely while the battery charger

is operational, or for a maximum of 5 minutes while the battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World-

wide Support Group. Please have the UPS model number and serial number available at the time of

your inquiry.

Table 4

Fault indicators

Indicator status

Diagnosis/Audible alarm

All indicators

On bypass due to output overload; beep every half-second

Indicator A

On bypass due to overtemperature condition on L1; 1-second beep every 4 seconds

On bypass due to overtemperature condition on L2; 2-second beep every 4 seconds

Indicator B

On bypass due to DC bus overvoltage on L1; 1-second beep every 4 seconds

On bypass due to DC bus overvoltage on L2; 2-second beep every 4 seconds

Indicator C

On bypass due to control power supply failure on L1; 1-second beep every 4 seconds

On bypass due to control power supply failure on L2; 2-second beep every 4 seconds

Indicator D

On bypass due to PFC failure on L1; 1-second beep every 4 seconds

On bypass due to PFC failure on L2; 2-second beep every 4 seconds

Indicator E

On bypass due to inverter failure on L1; 1-second beep every 4 seconds

On bypass due to inverter failure on L2; 2-second beep every 4 seconds

Indicators A&B

Inverter-to-Inverter communications failure; half-second beep every 1 second

Indicators A&C

UPS failed battery test; 2-second beep every 60 seconds

Indicators A&D

L1 to L2 phase angle unacceptable

Indicators B&C

REPO is currently activated, UPS output cannot be started by any method

Indicators B&D

UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power is

restored, press the OFF button twice within four seconds (to clear the alarm), then press the

ON button to start UPS (Auto-restart is NOT possible).

Indicators C&E

UPS shutdown due to command from communications (RS232 or SNMP); no beep

Indicators D&E

UPS is OFF due to charger overvoltage; 1-second beep every 4 seconds

AC Input indicator On &

Battery indicator Flashing

AC input has been applied to start UPS but the batteries are either missing or below the

minimal level to allow the UPS to start; continuous audible alarm

Bypass indicator Flashing

Bypass voltage is present, but is disabled for use because the voltage or frequency is outside

acceptable limits

Fault

indicator

A

B

C

D

E

Bypass

indicator

UPS ON indicator

Battery indicator

AC Input

indicator

Load Level

indicators

Battery

indicators

Advertising