Modes of Operation

30

10.0 M

ODES

OF

O

PERATION

10.1 Normal Mode Operation

During normal operation, utility power provides energy to

the UPS. The filters, power factor correction circuit and the

inverter process this power to provide computer grade

power to connected loads. The UPS maintains the batteries

in a fully charged state. The four green Load Level indica-

tors display an approximate level of load in 25% increments.

If the UPS becomes loaded beyond full rating, the fifth

(amber) indicator will illuminate and the UPS will sound an

audible alarm. The display template indicates the percent-

age of load (see example at right) on the UPS output.

10.2 Battery Mode Operation

Battery mode occurs in event of an extreme input voltage

condition or complete utility failure. The battery system

supplies power through the DC to DC converter to the

inverter to generate power for the connected load. During

battery mode an alarm sounds every 10 seconds. This will

change to two beeps every 5 seconds when the battery runs

low (approximately 2 minutes remaining, but this is user

configurable). The AC Input indicator will extinguish and

the Battery indicator will illuminate to warn that a utility

problem has occurred. Each Battery Level indicator repre-

sents a 20% capacity level. As capacity decreases, fewer

indicators remain illuminated. Refer to 13.0 - Trouble-

shooting. For approximate battery run times, refer to

Table 7 - Battery run times. These times are approximate

based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn off

non-essential pieces of equipment (such as idle computers and monitors) or add the optional external

battery cabinet.

10.3 Battery Recharge Operation

Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger

begins recharging.

!

CAUTION

Turning OFF the UPS while in battery mode will result in loss of output power.

Normal Mode Operation

Batteries at 100% charge

L1 Load at 10%, L2 Load at 90%

Battery Mode Operation

Batteries at 30% charge

L1 Load at 60%, L2 Load at 60%