3 establishing communication link with the ups, Establishing communication link with the ups – Liebert GXT2-6000 RT208 User Manual

Page 27

Advertising
background image

Configuration Program

21

8.3

Establishing Communication Link with the UPS

Use only the serial communication cable supplied with the configuration program. If an accessory

communication card has been installed in the UPS’s communication card slot, the option card must be

removed while using the configuration program.
Use the serial communication cable to connect your computer’s COM1 port to the DB-9 communica-

tion port on the rear of the UPS. COM2 may also be used. If the COM port of the host computer has

only a DB-25 pin connector, a DB-25 to DB-9 adapter must be added.
The program may be used while the UPS is on to read and confirm the current settings. The UPS

must be off and powered by the AC utility when using the configuration program to change any UPS

setting. Any attempt to change a setting while the UPS is on will result in an error message.
Select Lbt_gxt2.exe from the program group to start the configuration program. The program will

search COM1 & COM2 for a properly connected GXT 2U™ UPS. When the UPS is found, the opening

program window will display the UPS model.
If the configuration program ever fails in its attempt to read data from a UPS, the error message

below will be displayed. The program must communicate with the UPS when it first opens, when a

new tab is opened and when the REFRESH, APPLY or OK buttons are pressed.

If this message is displayed, check the following items:
1. Verify that the serial communication cable is connected properly.
2. Verify that the COM port being used is designated COM1 or COM2.
3. Verify that the UPS is either in Inverter mode, Bypass mode, Battery mode or Off with AC power

available at the input (AC Input indicator on). In all cases, the rear fan will be running.

4. Verify that the COM port is not in use by other UPS communication software (or non-UPS

software). If MultiLink UPS software is installed on the computer, the MultiLink service must be

stopped to free the COM port. MultiLink typically restarts automatically whenever the computer

restarts.

5. The UPS serial port is in use by an internal, optional communication card in the UPS card slot.

Remove the option card.

6. The program is connected to a UPS that was not designed for this program.