12.2 UPS Replacement

When using a power distribution box with bypass, the UPS can be removed while powering the load

through the Bypass Switch.

To remove the UPS without shutting off power to the connected load:
1. Turn the Bypass Switch on the power distribution box to the Utility position.
2. Open the Output circuit breaker (on the UPS rear panel).
3. Open the Input circuit breaker (on the power distribution box).
4. Loosen the three captive mounting screws about

20 turns until the power distribution box can be

pulled away from the UPS.

5. Loosen the electrical connector cover by backing

out the two screws holding it one turn each. Also

loosen the end screw one turn.

6. Slide the cover to reach the end screw and cover

the electrical connectors; retighten the three

screws gently to hold the cover in place.

7. Replace the UPS.
8. Loosen the three screws holding the electrical

connector cover again—one turn each.

9. Slide the cover away from the electrical

connectors; gently retighten the three screws.

10. Align the connectors on the power distribution

box and the UPS.

11. Push the power distribution box into place.
12. Holding the power distribution box firmly

against the UPS, tighten the three captive

mounting screws until the box is secure. Do NOT

overtighten the screws.

13. Close the Input circuit breaker (on the power

distribution box).

14. Close the Output circuit breaker (on the UPS

rear panel).

15. Turn the Bypass Switch on the power

distribution box back to the UPS position.

NOTE
During the procedure, the connected load will not be protected from power disturbances, such

as spikes, sags and failure.

DISCONNECT BYP

ASS PO

WER T

O

THE MANU

AL BYP

ASS SWIT

CH.

Mounting screws

for removable power

distribution box

Screws securing electrical

connector cover

Electrical

connector

cover

Electrical connectors