Connect Input/Output Power

The UPS ships with the basic hardwire box attached. If an

optional model is to be used, remove the standard box and

install the optional box using the three captive mounting

screws marked in the illustration, below, right.

6.3.1 Replacing a power distribution box

Whenever a power distribution box is not attached to a UPS,

the cover must be slid over the electrical connectors to prevent

damage or injury.
1. On the power distribution box attached to the UPS,

locate the three captive mounting screws holding the box

to the UPS (see illustration above, right).

2. Turn the screws until the box can be pulled away from the

UPS. Exercise care to avoid removing screws from the

hardwire box.

3. On the replacement power distribution box to be

attached to the UPS, loosen the cover over the electrical

connectors by backing out the three screws one turn each.

4. Slide the cover open to expose the electrical connectors.
5. Gently retighten the three screws loosened in Step 3.
6. Align the connectors on the box and UPS.
7. Push the box into place.
8. Holding the box firmly against the UPS, tighten the three

captive mounting screws until the box is secure. Do not

overtighten.

6.3.2 Distribution Box Electrical Connections

Electrical connections are made through a removable power distribution box that attaches to the rear

of the UPS.
The installer must provide a 30A branch circuit breaker. The input circuit breaker on the distribution

box and the output circuit breaker on the rear fixed-panel of the UPS disconnect all power between

the main cabinet and the distribution box.
Models equipped with a manual bypass switch pass utility power directly to the bypass switch from

the input terminal block. The input circuit breaker on the distribution box does not disconnect power

from the manual bypass switch.

Figure 3

30A branch circuit breaker connection diagram

DISCONNECT BYP

ASS PO

WER T

O

THE MANU

AL BYP

ASS SWIT

C

H.

Mounting screws

for removable box

Slide

cover

over

connec-

tors

Loosen screws

to move cover

PD-HDWR Distribution Box

PD-HDWR-MBS Distribution Box

Utility

Utility

Input

Input

Output

Output

30A External

Branch Circuit

Breaker

30A External

Branch Circuit

Breaker

30A Input

Circuit

Breaker

30A UPS Output

Circuit Breaker

30A UPS Output

Circuit Breaker

30A Input

Circuit

Breaker

Byp

Inv

UPS - PFC, Battery, Inverter

UPS - PFC, Battery, Inverter

Advertising