background image

Communications

33

11.4 Remote Emergency Power Off

The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS

input feeder breaker to remove all sources of power to the UPS and connected equipment to comply

with national and local wiring codes and regulations.

Figure 5

REPO switch connections

!

CAUTION

To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should

be segregated and run separately from power cables.

REPO connections

for normally open

switch system

REPO

as shipped

REPO connections

for normally closed

switch system (fail-safe)

1 2 3 4

Key to REPO switch connections
1.

24 VDC

2.

Sense

3.

Sense

4.

Ground

REPO Connection

1 2 3 4

1 2 3 4