8 battery tab, 1 low battery time warning, 2 auto battery test time – Liebert GXT2-6000 RT208 User Manual

Page 32: 3 battery cabinets number, 4 auto battery test, Battery tab, Low battery time warning, Auto battery test time, Battery cabinets number, Auto battery test

Advertising
background image

Configuration Program

26

8.8

Battery Tab

Factory default settings illustrated.
The boxes on the right show the available options using the drop-down selection boxes.

8.8.1 Low Battery Time Warning

The UPS will estimate remaining operating time when on batteries. A low battery alarm is activated

if the estimated time reaches the Low Battery Time. This may be changed to any value from 2 to 30

minutes.

8.8.2 Auto Battery Test Time

The UPS performs an automated battery test periodically, if enabled. The user may also select time

periods of 7, 14, 21 and 28 days.

8.8.3 Battery Cabinets Number

If additional batteries are attached to the UPS, accurate battery runtime estimates are possible if the

battery number and type of batteries are entered here. The new UPS models are designed to operate

with up to four external battery packs or four long runtime battery packs (not currently available).

8.8.4 Auto Battery Test

In some applications it may be preferable to disable the automated, periodic battery test. Click on the

box to remove the check mark and disable the periodic battery test.