4 install the grounding electrode conductor, 5 install the internal battery pack, Install the grounding electrode conductor – Liebert GXT2-6000 RT208 User Manual

Page 22: Install the internal battery pack

Advertising
background image

Installation and Configuration

16

6.4

Install the Grounding Electrode Conductor

A Grounding Electrode Conductor must be attached to the rear panel using the M5x12 Phillips screw

provided. This connection is required in addition to the power input ground connection to the remov-

able power distribution box.
Install an 8 AWG (10 mm

2

) (75°C copper wire) (minimum size, see NEC 250-5d, 250-81, 250-83, table

250-94) grounding electrode conductor to the nearest effectively grounded metal structural member,

nearest effectively grounded metal water pipe or other grounding electrode in the grounding electrode

system. If the grounding electrode conductor must be protected, non-metal conduit is recommended. If

metal conduit must be used, bond both ends of the conduit to the grounding electrode conductor. Con-

duit is not an acceptable grounding electrode conductor.
A 5mm ring lug for 8AWG wire lug is provided in the accessory box. Other suitable connectors may be

used.

6.5

Install the Internal Battery Pack

To facilitate shipping and installation, the GXT2-6000RT208 ships

without the internal battery installed. Once the UPS is installed in

place, the internal battery pack must be installed.
1. Unpack the internal battery from its shipping container.
2. Lift the battery pack from its container, holding it in the center

of the pack. Do NOT lift the battery pack by grasping the

connector on the rear.

3. Align the battery pack so that the rear connector is nearest the

control panel.

4. Slide in the battery pack until fully inserted.
5. Install the battery door, tightening the two captive screws, finger

tight. The battery door will not install if the battery is not fully

inserted.

6. For tower installation, place the horizontal overlay over the

controls and indicators (see illustration at right).

7. Install the two front bezels.

NOTE
IN BATTERY MODE ONLY, the UPS operates as a separately derived source and contains a

neutral to ground bonding jumper. A grounding electrode conductor (GEC) must be installed

in accordance with national and local wiring codes and regulations.

+

+

GROUNDING ELECTRODE CONDUCT

OR

Ground Electrode System

or Protective Earth System

Screws

for battery

door

Controls

and

Indicators

!

Liebert

!

!

!

!

+

-

12Vx1

2(

144

V)

9A

hi45

W

WAR

NING:

ADVERTENCIA:

AV

ERTISSEMENT

:

Battery

Compartment

Battery

Battery cover

Front bezels

Back of

battery

Battery

connector

Advertising