0 specifications, Table 8 ups specifications, Pecifications – Liebert GXT2-6000 RT208 User Manual

Page 47: Table 8, Ups specifications, 0 - specifications ). external battery

Advertising
background image

Specifications

41

14.0 S

PECIFICATIONS

Table 8

UPS specifications

Model Number

GXT2-6000RT208

Model Rating

4200W/5200VA at 127/220 (120 or 240 degrees only)

4200W/5200VA at 120/208 (120 or 240 degrees)

4200W/6000VA at 120/240 (180 degrees)

4200W/6000VA at 115/230 (180 degrees only)
3780W/5400VA at 110/220 (180 degrees only)
3360W/4800VA at 100/200 (180 degrees only)

DIMENSIONS in (mm)

Unit W x D x H in. (mm)

6.9 x 24.2 x 16.9 (176 x 615 x 430)

Shipping W x D x H in. (mm)

13.2 x 27.8 x 20.9 (335 x 705 x 530)

WEIGHT lbs (kg)

Unit

67 (30.3)

Shipping

76.3 (34.6)

INPUT AC PARAMETERS

Nominal Operating Frequency

50 or 60 Hz (Factory Default = 60)

Factory Default VAC

120/208 VAC at 120 degrees

L1-L2 Factory Default Input Phase

Angle

120 degrees

Allowable Input Phase Angle

120, 180, 240 degrees, Auto-sensing on application of AC

(Restrictions for L-N voltages other than 120 VAC)

Factory Default L1-N, L2-N VAC

120 VAC nominal

User Configurable L1-N, L2-N VAC

100/110/115/120/127 VAC (May be modified using configuration program)

L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)

100% - 90% loading

90 VAC - 140 VAC

90% - 70% loading

80 VAC - 140 VAC

70% - 30% loading

70 VAC - 140 VAC

30% - 0% loading

60 VAC - 140 VAC

L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)

100% - 70% loading

80 VAC - 140 VAC

70% - 30% loading

70 VAC - 140 VAC

30% - 0% loading

60 VAC - 140 VAC

L1-N, L2-N Max. Allowable VAC

150 VAC

Input Frequency w/o Battery

Operation

40 - 70 Hz

Input Power Connection

See Distribution Box Options

OUTPUT AC PARAMETERS

Factory Default VAC

120/208 VAC @ 120 degrees

L1-L2 Factory Default

Output Phase Angle

120 degrees

Allowable Output Phase Angle

120, 180, 240 degrees Auto-sensing on initial application of input AC

Factory Default L1-N, L2-N VAC

120 VAC nominal

User Configurable L1-N, L2-N VAC

100/110/115/120/127 VAC, ±3%

Output Connections

See Distribution Box Options

Frequency

50 Hz or 60 Hz, Nominal

Waveform

Sinewave

Main Mode Overload

200% for 8 cycles; 130% for 10 seconds with transfer to bypass

Bypass Protection Limits

Disable Bypass operation

If input voltage exceeds ±15% of the nominal voltage

Re-enable Bypass operation

If input voltage returns to within ±10% of nominal output voltage

Disable Bypass operation

When the input frequency prevents synchronous operation