Installation and Configuration

15

6.3.3 PD-HDWR and PD-HDWR-MBS Terminal Block Connections

Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not

share the same conduit.

The standard PD-HDWR comes installed on the UPS. The PD-HDWR-MBS with manual bypass

switch is optionally available. Both have the same hardwire terminal connections.

For best performance, distribute all L-N loads evenly between L1 and L2.

6.3.4 PD-001 Power Distribution Box

An optional PD-001 is available to provide the conve-

nience of an L14-30P input plug and output receptacles.

To use this box, remove the original PD-HDWR hardwire

box and install the PD-001.

Table 1

Electrical requirements—PD-HDWR and PD-HDWR-MBS

Input Current

Rating

Recommended (Max.)

External Overcurrent

Protection

Recommended Wire

(including ground wire)

(75°C copper wire)

Maximum Wire

Accepted by

Terminal Block

Terminal

Tightening

Torque

24A

30A

10 AWG

8 AWG

20 in-lb

NOTE
1. The installer must provide circuit breaker protection according to local codes. The utility

disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain

service space around the UPS or use flexible conduit.

2. The installer must provide output distribution panels, circuit breaker protection or

emergency disconnects according to local codes. Output circuits must not share a common

conduit with any other wiring.

Table 2

Electrical requirements—PD-001

Input Current

Rating

Recommended (Max.)

External Overcurrent

Protection

Required Utility

Receptacle

24A

30A

NEMA L14-30R

N

L2

L1

N

L2

L1

N

L2

L1

OUTPUT

INPUT

30A Max. Branch

Overcurrent Protection

8-10 AWG - USE COPPER WIRE ONLY - 20 in-lb - Strip 7mm

0

12

0

1

20

2

08 or

2

40

Output to Load - See Note 1

0

120

120

208
o

r 240

N

L2

L1

Input to UPS - See Note 2

Manual

Bypass

Switch

Output

Receptacles