Installation and Configuration

13

6.2

External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery

run time. External battery cabinets are designed to be placed on one side of the UPS or stacked

beneath the UPS.

When the external battery cabinet is received, it should be inspected for freight damage. Report dam-

age to the carrier and your local dealer or Liebert representative.
To install an external battery cabinet:
1. For slide rail installations, first remove the top/side fin by sliding it forward and lifting it up.

Optional rack-mount handles are shipped with the external battery cabinet and may be installed

now. (Securing hardware and slide rails are sold separately. Please contact your local dealer or

Liebert representative for these additional options and any assistance needed.)

2. Fasten the slides into position with the screws according to the instructions included with the

slide rails.

3. Use the enclosed support bases for the tower option to

prevent the assembly from tipping over. One additional set

of support base extensions ships with each external battery

cabinet.

4. Connect the supplied external battery cabinet cable to either

of the connectors on the rear of the external battery cabinet,

then to the rear of the UPS.

5. The UPS is now equipped with additional backup battery

run time. For approximate battery run times, refer to Table

7 - Battery run times in this manual.

6. Do NOT turn on the battery cabinet circuit breaker at this

time. Please complete the remainder of the installation first.

!

CAUTION

The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery

cabinets can be used in rack-mount or tower configuration. Take proper precautions when

lifting them.

!

CAUTION

Verify that the battery cabinet circuit breaker is in the OFF position. Do no energize the

battery cabinet at this time. When installation is complete, you will be instructed to turn on

the circuit breaker.

NOTE
After installation is complete, you must use the included

configuration program to program the UPS for the

number of external battery cabinets connected.

Instructions for using the configuration program follow

in 8.0 - Configuration Program.

+

+

-

-