Table 9 battery specifications, Table 10 power distribution box specifications, Table 9 – Liebert GXT2-6000 RT208 User Manual

Page 48: Battery specifications, Table 10, Power distribution box specifications

Advertising
background image

Specifications

42

ENVIRONMENTAL

Operating Temp

+32°F to +104°F (0°C to +40°C)

Storage Temp

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

Storage Elevation

50,000 ft. (15,000 m) maximum

Audible Noise

<55 dBA, at 1 meter from the rear

<50 dBA, at 1 meter from the front or sides

AGENCY

Safety

UL 1778, c-UL Listed (Suitable for computer room applications)

RFI/EMI

FCC Part 15, Subpart B, Class A

Surge Immunity

IEEE/ANSI C62.41 Category A & B

Transportation

ISTA Procedure 1A

Table 9

Battery specifications

Model Number

GXT2-144BATKIT

DIMENSIONS in (mm)

Shipping W x D x H in. (mm)

13.4 x 27.2 x 13.4 (340 x 690 x 340)

WEIGHT lbs (kg)

Unit

79 (35.8)

Shipping

84 (38.1)

Type

Valve-regulated, non-spillable, flame retardant, lead acid

Quantity x V x Rating

12 x 12V x 9.0 AH

Battery Mfg / Part #

Yuasa / REW 45-12 FR

Back-Up Time

See Table 7 - Battery run times

Recharge Time

6 Hours to 90% capacity after full discharge into 100% load

Table 10

Power distribution box specifications

Model Number

PD-HDWR

Amp Rating

24 Amps

Input Power Connection

4-Wire Hardwired, 8-10AWG

Output Power Connection

4-Wire Hardwired, 8-10AWG

Input Branch Circuit Breaker

30 Amp, Supplied by User

Model Number

PD-HDWR-MBS

Amp Rating

24 Amps

Input Power Connection

4-Wire Hardwired, 8-10AWG

Output Power Connection

4-Wire Hardwired, 8-10AWG

Includes:

Manual Bypass Switch with Indicator Lamps

Input Branch Circuit Breaker

30 Amp, Supplied by User

Model Number

PD-001

Amp Rating

24 Amps

Input Power Connections

L14-30P on 10 foot cord

Output Power Connection

L1-L2-G

(1) L6-30R on a 300mm cord

L1-L2-N-G

(1) L14-30R on a 300mm cord

L1-N-G

(2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers

L2-N-G

(2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers

Includes:

Manual Bypass Switch with Indicator Lamps

Input Branch Circuit Breaker

30 Amp, Supplied by User

Table 8

UPS specifications (continued)

Model Number

GXT2-6000RT208

Advertising