Configuration Program

23

8.5

UPS Tab

When the program starts, the following window will open displaying the UPS model along with the

current UPS settings. This information can be updated at any time using the REFRESH button.

Figure 4

Factory default settings for 120VAC UPS

8.5.1 Output Voltage

The Output Voltage displayed is the nominal input/output voltage. This is not a voltmeter and will

display the nominal voltage whether the UPS is on or off. The drop down box will show the alternate

voltages available. Select the voltage that matches the nominal utility in your location.

8.5.2 Auto Restart

The UPS will provide computer grade power during power outages. If input power is unavailable for

an extended time, the UPS will shut down when batteries are depleted or a shutdown signal is sent by

the computer operating system to limit battery depletion (serial data or contact closure). If Auto

Restart is enabled (check mark in box), the UPS will restart when input power is restored. If the UPS

turns off power to the load for any other reason, manual restart is required (See 8.6 - Options Tab

for exceptions). Click on the box to remove the check mark and disable Auto Restart.

8.5.3 L-N Reverse Detection (120V UPS Models Only)

Proper wiring of the receptacle powering the UPS is critical for safety, EMI suppression and surge

suppression. The UPS checks the outlet when first plugged in. If the Line-Neutral is reversed or the

ground is missing, the UPS will not start. If a problem is detected after the UPS is started, the UPS

will continue to operate, but the AC Input indicator will flash. In some unique applications the user

may wish to disable this alarm. Except for special situations, improperly wired receptacles should be

immediately repaired before the UPS is put into service. Click on the box to remove the check mark

and disable this alarm.