Table 7 battery run times, Table 7, Battery run times – Liebert GXT2-6000 RT208 User Manual

Page 45: Table, 7 - battery run times

Advertising
background image

Troubleshooting

39

Using the configuration program, the user may specify the number of GXT2-144VBATT external bat-

tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 7 shows estimated run times at different loads.
Table 7

Battery run times

Battery/External Cabinets

Load%

6000VA Run Time

in Minutes

Internal Battery

10%

75

20%

38

30%

25

40%

18

50%

14

60%

11

70%

9

80%

7

90%

6

100%

5

Internal Battery + 1 External

Battery Cabinet

10%

156

20%

90

30%

62

40%

44

50%

34

60%

28

70%

23

80%

19

90%

16

100%

14

Internal Battery + 2 External

Battery Cabinets

10%

235

20%

137

30%

99

40%

74

50%

58

60%

47

70%

39

80%

33

90%

28

100%

25

Internal Battery + 3 External

Battery Cabinets

10%

313

20%

183

30%

133

40%

103

50%

82

60%

67

70%

55

80%

47

90%

41

100%

36

Internal Battery + 4 External

Battery Cabinets

10%

391

20%

229

30%

166

40%

129

50%

105

60%

87

70%

73

80%

63

90%

54

100%

47