8.5.4 Frequency Selection

The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the

model. All models are capable of being used as 50Hz or 60Hz systems. The UPS will automatically

sense the utility frequency when first plugged in and set the nominal frequency to match. Therefore,

for all normal use the Auto Sense button should be selected.
Some special applications require that the UPS be used as a frequency converter. Frequency con-

verter 50Hz or frequency converter 60Hz may be selected.
Note that frequency converter operation disables the Bypass. If, for any reason, the UPS inverter is

unable to power the load, the alternate bypass to utility power will not be available and power will be

removed from any load.

8.6

Options Tab

Computer users may choose to use versatile com-

puter shutdown software that communicates

with the UPS via a serial communications cable.

The Options tab should not be used to modify the

UPS functions for such applications.
For some industrial applications and special

computer applications, the UPS may be moni-

tored and controlled using external voltages and

relay contact signals. The Options tab expands

the UPS versatility for such applications.
Refer to your UPS manual for a description of the

9-pin communication connector on the rear of the

UPS. Pin 6 of the 9-pin communication connector

is used for “Any Mode Shutdown” of the UPS out-

put. This control input may be used in special

applications to disable the UPS output power -

both Inverter and Bypass.
The Options tab allows the behavior of the Any

Mode Shutdown feature to be modified.
When the program opens or the REFRESH but-

ton is pressed, the UPS setting is read by the

configuration program and displayed.
Factory Default Setting Illustrated - This

Options tab illustration shows the available

function definitions using pin 6 and the factory

default settings.

!

WARNING

Auto-Enable Output
Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS

output can turn on automatically and without warning if the Pin 6 connection is changed.

!

WARNING

Pin 6 Logic
DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to

install a normally-closed connection between Pins 5 & 6. This connection must be maintained

to use the UPS or to use the configuration program again, including the ability to change the

UPS setting back to the default setting using the configuration program via a serial

communication link.