Perle Systems IOLAN SDS User Manual

Page 151

Advertising
background image

I/O Commands 151

Set IOChannel

range

Specify the temperature range that you want to measure. For RTD, the range is:

z

1 (Pt100 a=385 -50 to 150C) This is the default.

z

2 (Pt100 a=385 0 to 100C)

z

3 (Pt100 a=385 0 to 200C)

z

4 (Pt100 a=385 0 to 400C)

z

5 (Pt100 a=385 -200 to 200C)

z

6 (Pt100 a=392 -50 to 150C)

z

7 (Pt100 a=392 0 to 100C)

z

8 (Pt100 a=392 0 to 200C)

z

9 (Pt100 a=392 0 to 400C)

z

10 (Pt100 a=392 -200 to 200C)

z

11 (Pt1000 a=385 -40 to 160C)

z

12 (NiFe604 a=518 -80 to 100C)

z

13 (NiFe604 a=518 0 to 100C)

For thermocouple, the range is:

z

b (B 500 to 1800C)

z

e (E 0 to 1000C)

z

j (J 0 to 760C) This is the default.

z

k (K 0 to 1370C)

z

r (R 500 to 1750C)

z

s (S 500 to 1750C)

z

t (T -100 to 400C).

alarm

Configures alarm settings when the Analog input trigger is activated.

level

You can specify up to five alarm trigger/clear severity levels. If the

Trigger Type

is

Low

, an alarm is triggered when the input drops below the specified

Trigger

value;

other severity level trigger values must decrease in value with each subsequent level. If

the

Trigger Type

is

High

, an alarm is triggered when the input is higher than the

specified

Trigger

value; other severity level trigger values must increase in value with

each subsequent level. To clear an alarm, the input must drop below the specified value

when

Trigger Type

is

High

or go above the specified value when

Trigger Type

is

Low

.

mode

Enables/disables an alarm level. The default is off.

trigger-type

If the

Trigger Type

is

Low

, an alarm is triggered when the input drops below the

specified

Trigger

value; other severity level trigger values must decrease in value with

each subsequent level. If the

Trigger Type

is

High

, an alarm is triggered when the input

is higher than the specified

Trigger

value; other severity level trigger values must

increase in value with each subsequent level.

trigger-level

Specify the value that will trigger an alarm, the measurement is based on the

Type

and

Range

that you specify. This value must not fall within the scope of the value used to

clear an alarm.