Chapter 4

Analog Input

© National Instruments Corporation

4-7

NI 6236 User Manual

Caution The maximum input voltage and current ratings of AI signals with respect to
AI GND (and for differential signals with respect to each other) and earth/chassis ground
are listed in the Maximum Working Voltage section of the NI 6236 Specifications.
Exceeding the maximum input voltage or maximum working voltage of AI signals distorts
the measurement results. Exceeding the maximum input voltage or maximum working
voltage rating also can damage the device and the computer. Exceeding the maximum input
voltage can cause injury and harm the user. NI is not liable for any damage or injuries
resulting from such signal connections.

AI ground-reference setting is sometimes referred to as AI terminal
configuration
.

Configuring AI Ground-Reference Settings in Software

You can program channels on an M Series device to acquire with different
ground references.

To enable multimode scanning in LabVIEW, use

NI-DAQmx Create

Virtual Channel.vi

of the NI-DAQmx API. You must use a new VI for

each channel or group of channels configured in a different input mode. In
Figure 4-6, channel 0 is configured in differential mode and
aignd_vs_aignd reads the internal analog input ground-reference of the
device.

Figure 4-6. Enabling Multimode Scanning in LabVIEW

To configure the input mode of your current measurement using the DAQ
Assistant, use the Terminal Configuration drop-down list. Refer to the
DAQ Assistant Help for more information about the DAQ Assistant.

To configure the input mode of your current measurement using the
NI-DAQmx C API, set the terminalConfig property. Refer to the
NI-DAQmx C Reference Help for more information.