Ai convert clock timebase signal, Ai hold complete event signal – National Instruments DAQ M Series User Manual

Page 44

Advertising
background image

Chapter 4

Analog Input

NI 6236 User Manual

4-20

ni.com

It is also possible to use a single external signal to drive both
ai/SampleClock and ai/ConvertClock at the same time. In this mode, each
tick of the external clock will cause a conversion on the ADC. Figure 4-13
shows this timing relationship.

Figure 4-13. Single External Signal Driving ai/SampleClock and ai/ConvertClock

Simultaneously

AI Convert Clock Timebase Signal

The AI Convert Clock Timebase (ai/ConvertClockTimebase) signal is
divided down to provide one of the possible sources for ai/ConvertClock.
Use one of the following signals as the source of
ai/ConvertClockTimebase:

ai/SampleClockTimebase

20 MHz Timebase

ai/ConvertClockTimebase is not available as an output on the I/O
connector.

AI Hold Complete Event Signal

The AI Hold Complete Event (ai/HoldCompleteEvent) signal generates a
pulse after each A/D conversion begins. You can route
ai/HoldCompleteEvent out to any output PFI <6..9> or RTSI <0..7>
terminal.

The polarity of ai/HoldCompleteEvent is software-selectable, but is
typically configured so that a low-to-high leading edge can clock external
AI multiplexers indicating when the input signal has been sampled and can
be removed.

• One External Signal Driving Both Clocks

ai/SampleClock

ai/ConvertClock

Sample #1 Sample #2 Sample #3

1 2 3

0

1 2 3

0

1 …

0

Channel Measured

Advertising