ni.com

Figure 5-6 shows the relationship of ao/SampleClock to ao/StartTrigger.

Figure 5-6. ao/SampleClock and ao/StartTrigger

AO Sample Clock Timebase Signal

The AO Sample Clock Timebase (ao/SampleClockTimebase) signal is
divided down to provide a source for ao/SampleClock.

You can route any of the following signals to be the AO Sample Clock
Timebase (ao/SampleClockTimebase) signal:

20 MHz Timebase

100 kHz Timebase

PXI_CLK10

Input PFI <0..5>

RTSI <0..7>

PXI_STAR

ao/SampleClockTimebase is not available as an output on the I/O
connector.

You might use ao/SampleClockTimebase if you want to use an external
sample clock signal, but need to divide the signal down. If you want to use
an external sample clock signal, but do not need to divide the signal, then
you should use ao/SampleClock rather than ao/SampleClockTimebase.

ao/SampleClockTimebase

ao/StartTrigger

ao/SampleClock

Delay

From

Start

Trigger