Buffered two-signal edge-separation measurement, Figure 7-20 sho – National Instruments DAQ M Series User Manual

Page 81

Advertising
background image

Chapter 7

Counters

© National Instruments Corporation

7-19

NI 6236 User Manual

Figure 7-20. Single Two-Signal Edge-Separation Measurement

Buffered Two-Signal Edge-Separation Measurement

Buffered and single two-signal edge-separation measurements are similar,
but buffered measurement measures multiple intervals.

The counter counts the number of rising (or falling) edges on the Source
input occurring between an active edge of the Gate signal and an active
edge of the Aux signal. The counter then stores the count in a hardware save
register. On the next active edge of the Gate signal, the counter begins
another measurement. A DMA controller transfers the stored values to host
memory.

Figure 7-21 shows an example of a buffered two-signal edge-separation
measurement.

Figure 7-21. Buffered Two-Signal Edge-Separation Measurement

For information about connecting counter signals, refer to the

Default

Counter Terminals

section.

AUX

Counter

Armed

8

0

0

0

0

1

2

3

4

5

6

7

8

8

8

Measured Interval

GATE

SOURCE

Counter Value

HW Save Register

SOURCE

Counter Value

Buffer

AUX

GATE

1

2

3

1

2

3

1

2

3

3

3
3

3
3
3

Advertising