18 installation, Vent requirements – Omni Group GREEN SMART 864 User Manual

Page 18

Advertising
background image

18 Installation

(for qualified installers only)

© Travis Industries

4090507

100-01217_000

Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and never be

attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas appliance

must use its own separate vent system.

In addition to the requirements listed here, follow the requirements provided with the vent.

A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through framing

members). Horizontal vent less than 48" (1219mm) above the fireplace must use the Travis Firestop (sku

93006094 - it incorporates a 3" (76mm) clearance above, 1" (25mm) clearance below and to the sides of the

vent). Other penetrations only require a 1" (25mm) clearance and may use a standard firestop (make sure

the required 1" (25mm) clearance is met).

Vent Clearances

The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill air

spaces with insulation.

Before 48" (1219mm) Rise

After 48" (1219mm) Rise

Sides

1" (25mm)

1" (25mm)

Above

3" (76mm)

1" (25mm)

Below Horizontal or 45° Section

1" (25mm)

1" (25mm)

Horizontal

Termination

Required Firestop

Min. 3" (76mm)
(1" or 25mm if a
minimum 48"or
1219mm above the
fireplace)

Min. 1" (25mm)

Min. 1" (25mm)

Use a firestop whenever

passing through a ceiling

Vertical Termination

Use a roof flashing and storm collar

whenever passing through the roof

Min. 1"(25mm)

Use a support box

on exposed vent

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet (1800 M). In this testing we have found that

the heater, with its standard orifice, burns correctly with just an air shutter adjustment.

Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard. Consult your

dealer or installer if you suspect an improperly adjusted air shutter.

Advertising