background image

24 Installation

(for qualified installers only)

© Travis Industries

4090507

100-01217_000

Side Vent Configuration with Horizontal Termination (with vertical rise)

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and diffuser

positions.

Up to four elbows (45° or 90°) may be used.

Only one horizontal elbow may be used.

5 feet (1.5m)

0 feet

0 feet

5 feet (1.5m)

0 feet

20 feet (6m)

20 feet (6m)

5 feet(1.5m)

10 feet (3m)

5 feet (1.5m)

10 feet (3m)

0 feet

15 feet (4.5m)

20' max (6m)

10 feet (3m)

15 feet (4.5m)

15 feet (4.5m)

20' max (6m)

10 feet (3m)

15 feet (4.5m)

22' max (6.7m)

22' max (6.7m)

Exhaust Restrictor # 2 (stock)
Intake Restrictor # 1 (stock)
Diffuser Position # 1

Exhaust Restrictor # 4
Intake Restrictor # 1
Diffuser Position # 1

Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 2 (stock)

This is considered a horizontal
elbow (it does not matter

whether it turns right or left).
It may be a 90° or 45° elbow.

This is considered a
vertical elbow

Horizontal length is calculated by adding

both lengths of horizontal run
(Horizontal Length = H1 + H2).

H1

H2