Installation – Omni Group GREEN SMART 864 User Manual

Page 23

Advertising
background image

Installation

(for qualified installers only)

23

© Travis Industries

4090507

100-01217_000

Side Vent Configuration with Horizontal Termination (no vertical rise)

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and diffuser

positions.

HINT: Travis Industries provides a minmum vent kit (sku 98900168). It includes a 4” (102mm) section and a

horizontal termination cap.

Optional 45° Elbow

Termination

See the charts below to
determine maximum vent

3 feet (0.915m)

0 feet

0 feet

4' max 1.22m)

• Exhaust Restrictor # 1 (stock)
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1

Vent with No 45° Elbow

Vent with 1 45° Elbow

• Min. 4" (102mm) Horizontal Section
• Max. 24" (610mm) Horizontal
Section(s)

• Min. 4" (102mm) Horizontal Section
• Max.48" (1219mm) Horizontal
Section(s)

• Exhaust Restrictor # 1 (stock)
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1

2' max (0.61m))

3 feet (0.915m)

0 feet

0 feet