Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09

38

3 fasteners

per side

Ceiling firestop

installed below ceiling.

Ceiling firestop

installed above ceiling.

Install attic insula-
tion shields before
or after installation
of vent system.

Attic Above

10 in. (254 mm)

Hole should measure

10 in. x 10 in.

(254 mm x 254 mm)

inside to inside

10 in.

(254 mm)

C. Install the Ceiling Firestop

A ceiling fi restop MUST be used between
fl oors and attics.

Frame an opening 10 in. by 10 in. (254 mm
by 254 mm) whenever the vent penetrates
a ceiling/fl oor (see Figure 8.4).

• Frame the area with the same sized lumber

as used in ceiling/fl oor joist.

• The

ceiling

fi restop may be installed above

or below the ceiling joists when installed
with a attic insulation shield. It must be
under joists between fl oors that are not
insulated. Refer to Figure 8.5.

• Secure with three fasteners on each side.

WARNING! Risk of Fire!

DO NOT pack insu-

lation around the vent. Insulation must be kept
back from the pipe to prevent overheating.

Figure 8.4

Installing Ceiling Firestop

Figure 8.5 Installing the Attic Shield