I. install horizontal termination cap – Quadra-Fire QFP38-NG User Manual

Page 47

Advertising
background image

Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09

47

INTERIOR

Heat Shield or

Extended

Heat Shield

Wall Shield

Firestop

Heat Shield

1-1/2 in. (38 mm) min.

overlap

SHEATHING

Slip Section

can be extended

Inner Vent

Outer Vent

EXTERIOR

Figure 10.16 Venting through the wall

Note: When using termination caps with factory-supplied
heat shield attached, no additional wall shield fi restop is
required on the exterior side of a combustible wall.

I. Install Horizontal Termination Cap

WARNING! Risk of Fire!

The telescoping fl ue section

of the termination cap MUST be used when connecting
vent.

• 1-1/2 (38 mm) minimum overlap of fl ue telescoping

section is required.

Failure to maintain overlap may cause overheating and
fi re.

Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.

• Flash and seal as appropriate for siding material at

outside edges of cap.

• When installing a horizontal termination cap, follow

the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 6 of this manual.

CAUTION! Risk of Burns!

Local codes may require

installation of a cap shield to prevent anything or anyone
from touching the hot cap.

NOTICE:

For certain exposures which require superior

resistance to wind-driven rain penetration, a fl ashing kit and
HPC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.

Advertising
This manual is related to the following products: