Gas information, Warning – Quadra-Fire QFP38-NG User Manual

Page 50

Advertising
background image

Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09

50

A. Gas Pressure

• Optimum appliance performance requires proper input

pressures.

Gas line sizing requirements will be determined in ANSI
Z221.3 National Fuel Gas Code in the USA and CAN/
CGA B149 in Canada.

• Pressure requirements are:

B. Gas Connection

Refer to Reference Section 17.A. for location of gas line
access in appliance.

• Gas line may be run through knockout(s) provided.
• The gap between supply piping and gas access hole

may be caulked with high temperature caulk or stuffed
with non-combustible, unfaced insulation to prevent cold
air infi ltration.

Ensure that gas line does not come in contact with outer
wrap of the appliance. Follow local codes.

• Pipe incoming gas line into valve compartment.
• Connect incoming gas line to the 1/2 in. (13 mm)

connection on manual shutoff valve.

WARNING! Risk of Fire or Explosion!

Support control

when attaching pipe to prevent bending gas line.

• A small amount of air will be in the gas supply lines.

WARNING! Risk of Fire or Explosion!

Gas build-up dur-

ing line purge could ignite.

• Purge should be performed by qualified service

technician.

• Ensure adequate ventilation.
• Ensure there are no ignition sources such as sparks or

open fl ames.

WARNING! Risk of Fire or Explosion!

High pressure

will damage valve. Low pressure may cause explosion.

• Verify inlet pressures. Verify minimum pressures when

other household gas appliances are operating.

• Install regulator upstream of valve if line pressure is

greater than 1/2 psig.

12

12

Gas Information

Gas Pressure

Natural Gas

Propane

Minimum inlet pressure

5.0 in. w.c.

11.0 in. w.c.

Maximum inlet pressure

10.0 in. w.c.

13.0 in. w.c.

Manifold pressure

3.5 in. w.c.

10.0 in. w.c.

Note: Have the gas supply line installed in accordance with
local codes, if any. If not, follow ANSI 223.1. Installation
should be done by a qualifi ed installer approved and/or
licensed as required by the locality. (In the Commonwealth
of Massachusetts installation must be performed by a
licensed plumber or gas fi tter).

Note: A listed (and Commonwealth of Massachusetts
approved) 1/2 in. (13 mm) T-handle manual shut-off valve
and fl exible gas connector are connected to the 1/2 in.
(13 mm) control valve inlet.

• If substituting for these components, please consult

local codes for compliance.

C. High Altitude Installations

NOTICE:

If the heating value of the gas has been reduced,

these rules do not apply. Check with your local gas utility or
authorities having jurisdiction.

When installing above 2000 feet elevation:

In the USA: Reduce burner orifi ce 4% for each 1000 feet
above 2000 feet.

• In CANADA: Reduce burner orifi ce 10% for elevations

between 2000 feet and 4500 feet. Above 4500 feet,
consult local gas utility.

Fire Risk.

Explosion Hazard.

High pressure will damage valve.

• Disconnect gas supply piping BEFORE

pressure testing gas line at test pressures
above 1/2 psig.

• Close the manual shutoff valve BEFORE

pressure testing gas line at test pressures
equal to or less than 1/2 psig.

WARNING

Light the appliance. It will take a short time for air to purge
from lines. When purging is complete the appliance will
light and operate normally.

WARNING! Risk of Fire, Explosion or Asphyxiation!

Check all fi ttings and connections with a non-corrosive
commercially available leak-check solution. DO NOT use
open fl ame. Fittings and connections could have loos-
ened during shipping and handling.

WARNING! Risk of Fire! DO NOT change valve settings.
This valve has been preset at the factory.

Note: Gas access is on the left side only.

Advertising
This manual is related to the following products: