E. install metal roof flashing, Caulk pipe flashing – Quadra-Fire QFP38-NG User Manual

Page 44

Advertising
background image

Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09

44

E. Install Metal Roof Flashing

• See minimum vent heights for various pitched roofs

(Figure 10.11) to determine the length of pipe to extend
through the roof.

• Slide the roof fl ashing over the pipe sections extending

through the roof as shown in Figure 10.12.

Horizontal
overhang

12

X

20 in.

(508 mm)

Lowest

Discharge

Opening

Termination

Cap

Roof Pitch
is X / 12

Vertical
wall

H (min.) - Minimum height
from roof to lowest
discharge opening.

24 in. min.

(610 mm)

Roof Pitch

H (Min.) Ft.

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0*

Over 11/12 to 12/12

4.0

Over 6/12 to 7/12

1.25*

Over 12/12 to 14/12

5.0

Over 7/12 to 8/12

1.5*

Over 14/12 to 16/12

6.0

Over 8/12 to 9/12

2.0*

Over 16/12 to 18/12

7.0

Over 9/12 to 10/12

2.5

Over 18/12 to 20/12

7.5

Over 10/12 to 11/12

3.25

Over 20/12 to 21/12

8.0

* 3 ft. minimum in snow regions

Storm Collar

Roof

Flashing

Figure 10.11 Minimum Height From Roof To Lowest Discharge
Opening

Figure 10.12

NOTICE:

Failure to properly caulk the roof fl ashing could

cause water entry.

Caulk the gap between the roof fl ashing and the outside
diameter of the pipe.

Caulk the perimeter of the fl ashing where it contacts the
roof surface. See Figure 10.12.

Caulk

Pipe

Flashing