Termination locations, Warning, A. vent termination minimum clearances – Quadra-Fire Expression 36 QV36A-FB User Manual

Page 11

Advertising
background image

11

Quadra-Fire • Expression 36 (QV36A-FB) • 2062-900 Rev. S • 11/11

A. Vent Termination Minimum Clearances

Fire Risk.

Explosion Risk.

Maintain vent clearance to combustibles as
specifi ed.

• Do not pack air space with insulation or other

materials.

Failure to keep insulation or other materials
away from vent pipe may cause fi re.

Roof Pitch

H (Min.) Ft.

Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0

Figure 4.1

Figure 4.2 Minimum height from roof to lowest discharge
opening

4

4

Termination Locations

Measure horizontal clearances from this surface.

Measure vertical clearances from this surface.

Figure 4.3 Multiple Vertical Termination

Figure 4.2 specifi es minimum vent heights for various
pitched roofs.

(See Figure 4.4 for specifi c clearances)

* 3 foot minimum in snow regions

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT
TERMINATION CAP

12

X

ROOF PITCH

IS X/ 12

LOWEST

DISCHARGE

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

Gas, Wood or Fuel Oil

Termination Cap

B

Gas

Termination

Cap **

A *

*

If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.

**

A

B

6 in. (minimum) up to 20 in.

152 mm/508 mm

18 in. minimum

457 mm

20 in. and over

0 in. minimum

In a staggered installation with both gas and wood or fuel oil
terminations, the wood or fuel oil termination cap must be
higher than the gas termination cap.

WARNING

Fire Risk.
Explosion Risk.
Inspect external vent cap regularly.
• Ensure no debris blocks cap.
• Combustible materials blocking cap may

ignite.

• Restricted air fl ow affects burner operation.

WARNING