Quadra-Fire Expression 36 QV36A-FB User Manual

Page 15

Advertising
background image

15

Quadra-Fire • Expression 36 (QV36A-FB) • 2062-900 Rev. S • 11/11

Figure 5.5

1. Top Vent - Horizontal Termination - (continued)

Three Elbows

H

T

V

T

H

2

H

1

V

2

V

1

V

T

Min.

H

T

Max.

1 ft. 6 in.

3 ft.

2 ft. 6 in.

6 ft.

3 ft. 6 in.

9 ft.

4 ft.

10 ft.

4 ft. 6 in.

12 ft.

5 ft. 6 in.

15 ft.

6 ft. 6 in.

18 ft.

7 ft. 6 in.

21 ft.

H

T

= 21 ft. Max

V

T

= 40 ft. Max

V

T

+ H

T

= 30 ft. Max*

Note: A section of vertical pipe (12 inches minimum)
MUST be installed prior to attaching a 90° elbow.

* If the horizontal component is less than

5 feet then the total vent run can be
extended to 40 feet.