Quadra-Fire • Expression 36 (QV36A-FB) • 2062-900 Rev. S • 11/11

14

Note: Must have a 12 inch minimum
vertical vent before attaching a 90° elbow
to the unit.

H

1

V

1

Figure 5.3

Figure 5.4

D. Vent Diagrams

1. Top Vent - Horizontal Termination

One Elbow

Two Elbows

* If the horizontal component is less than

5 feet then the total vent run can be
extended to 40 feet.

INSTALLED

HORIZONTALLY

H

1

H

2

V

1

V

1

Minimum

H

1

Maximum

1 ft.

305 mm

3 ft

924 mm

2-1/2 ft.

762 mm

6 ft

1.8 m

3-1/2 ft.

1.7 m

9 ft

2.7 m

4 ft.

1.2 m

10 ft

3.1 m

4-1/2 ft.

1.4 m

12 ft

3.7 m

5-1/2 ft.

1.7 m

15 ft

4.6 m

6-1/2 ft.

2 m

18 ft

5.5 m

7-1/2 ft.

2.3 m

21 ft

6.4 m

H

1

= 21 ft. (6.4 m) Maximum

V

1

= 40 ft. (12.2 m) Maximum

V

1

+ H

1

= 30 ft. (9.1 m) Maximum*

Fire Risk. Explosion Risk.

Do NOT pack insulation or other combustibles between ceiling fi restops.

• ALWAYS maintain specifi ed clearances around venting and fi restop systems.

• Install wall shield and ceiling fi restops as specifi ed.

Failure to keep insulation or other material away from vent pipe may cause fi re.

WARNING

V

1

Minimum

H

1

+ H

2

Maximum

1 ft.

305 mm

3 ft

924 mm

2-1/2 ft.

762 mm

6 ft

1.8 m

3-1/2 ft.

1.7 m

9 ft

2.7 m

4 ft.

1.2 m

10 ft

3.1 m

4-1/2 ft.

1.4 m

12 ft

3.7 m

5-1/2 ft.

1.7 m

15 ft

4.6 m

6-1/2 ft.

2 m

18 ft

5.5 m

7-1/2 ft.

2.3 m

21 ft

6.4 m

V

1

= 40 ft. (12.2 m) Maximum

H

1

+ H

2

= 21 ft. (6.4 m) Maximum

V

1

+ H

1

+ H

2

= 30 ft. (9.1 m) Maximum*

* If the horizontal component is less than

5 feet then the total vent run can be
extended to 40 feet.

Note: Must have a 12 inches minimum
vertical vent before attaching a 90° elbow
to the unit.