Quadra-Fire • Expression 36 (QV36A-FB) • 2062-900 Rev. S • 11/11

34

Setting Flame Height/manifold pressure

(To be done by a qualifi ed service technician). Upon initial
power-up of this device, valve pressure must be set for
fl ame adjustment.

• Loosen output pressure tap on valve and connect with

pressure manometer.

• Press fl ame button once (Fig. 10.4); fi replace will light

with fl ames on high.

• Turn solenoid clockwise to increase pressure,

counterclockwise to decrease pressure until manifold
pressure on high is 3.5” water column for natural gas
(NG), 10.0” water column for propane (LP).

• Once pressure is achieved spin jam-nut on solenoid

stem tight against regulator face to prevent rotation. Do
not overtighten.

• Press fl ame button twice to turn fi replace off.

• Remove manometer tube and tighten or close pressure

tap. Use a soap solution to carefully check the pressure
tap for leaks.

Wall Switch Button Operation

See Figure 10.4.

Flame Button

• Button Press: Unit On / Flames High, Turns on auxiliary

power

• Button Press: Flames Low

• Button Press: Unit Off / Flames Off, Turns off auxiliary

power

Fan / Blower Button

• Button Press: Fan High (“3”)

• Button Press: Fan Medium (“2”)

• Button Press: Fan Low (“1”)

• Button Press: Fan Off

Temperature Button

• Button Press will toggle between Automatic and Manual

Operation

• Press and Hold the button for 3 seconds to toggle between

Fahrenheit and Centigrade Temperature Display.

Automatic Operation: Controller will monitor temperature

and control unit according to the set point.

Manual Operation: Controller will not automatically
change settings.

SET Set Temperature Button

• Button Press: Displays Set Point

• Use Up and Down Arrows to Adjust Set Point

• Press Set Button to Store New Set Point

Temperature Set Point can be adjusted between the ranges of:

45-90

0

Fahrenheit or 7-32

0

Centigrade

NOTE: The controller will turn off the fi replace at 2

0

F over

set point and turn it back on at 2

0

F below set point.

<>

Up and Down Arrows

• Push to adjust set point temperature under automatic

control.

AUX Auxiliary Button

• Button Press: Turns on auxiliary power

• Button Press: Turns off auxiliary power

Can be operated independently of all functions

.

Child Proof Mode

To Enter Child Proof Mode:

• Press the Up Arrow Button twice and Down Arrow Button

once. The unit will send out 3 beeps and an indicator in
the LCD panel will show that the child proof is on.

To Leave Child Proof Mode:

• Press the Up Arrow Button twice and Down Arrow Button

once. The unit will send out 3 beeps and the indicator in
the LCD panel that shows that the child proof is on will
disappear.

NOTE: When in Child Proof Mode, only the arrow buttons
will have functionality. Unit can enter Child Proof when the
fi replace is on or off.

INTELLIFIRE (IPI) MODELS ONLY

Cold Climate Button

• Button Press: Turns on Climate Control

• Button Press: Turns off Climate Control

This allows the pilot fl ame to stay lit when activated, a
benefi t of this is reduced condensation on the glass at
start-up in colder climate conditions
.

Operation Under Battery Power

A switch on the control box allows for battery power under
no-power conditions. See Figure 10.6. By controlling the
power supply with this switch, the batteries are supplying
power only when needed, thus extending battery life. The
switch also provides a convenient means for switching to
battery power should there be a loss of 110 VAC power to
the control box.
• In the event of a power failure, switch the battery

operation switch to the “Battery ON” position.

• The fi replace can now be turned on and off with the ON/

OFF rocker switch located near the gas valve.

• The wall switch functions will not operate under battery

power.

• Under battery control the only available function is fl ame

“On” and “Off” in the high position.

• To maximize battery life, and to restore full function

capability of the wall switch, fl ip switch to “OFF” position
after 120 VAC power is restored.