Vent clearances and framing, Warning – Quadra-Fire Expression 36 QV36A-FB User Manual

Page 18

Advertising
background image

Quadra-Fire • Expression 36 (QV36A-FB) • 2062-900 Rev. S • 11/11

18

A. Pipe Clearances to Combustibles

6

6

Vent Clearances and Framing

B. Wall Penetration Framing

Combustible Wall Penetration

Frame a hole in a combustible wall for an interior wall
shield fi restop, (Figure 6.2) whenever a wall is penetrated.
Use same size framing materials as those used in the wall
construction. The wall shield fi restop maintains minimum
clearances and prevents cold air infi ltration.

Non-Combustible Wall Penetration

If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter one
inch greater than the pipe is acceptable.

Whenever a non-combustible wall is penetrated, the wall
shield fi restop is only required on one side and no heat
shield is necessary.

If your local inspector requires the wall shield fi restop on
both sides, then both wall shield fi restops must have a heat
shield attached to them.

Fire Risk.

Explosion Risk.

Maintain vent clearance to combustibles as
specifi ed.

• Do not pack air space with insulation or

other materials.

Failure to keep insulation or other materials
away from vent pipe may cause fi re.

Figure 6.1 Pipe Clearances

1 in. CLEARANCE

AROUND VERTICAL

SECTIONS

3 in. TOP

CLEARANCE

1 in. SIDE AND

BOTTOM CLEARANCE

Figure 6.2 Exterior Wall Hole

* Shows center of vent framing hole for top venting.

The center of the hole is one (1) inch (25.4 mm)
above the center of the horizontal vent pipe.

53-3/4 in.
1365 mm

54-3/4 in.
1391 mm

VENT FRAMING HOLE*

(Do NOT pack with

Insulation)

WARNING

Note: The top standoff is fl at on top of the unit for shipping
purposes. The two pieces should be folded up as shown
and connected together by interlocking tabs and slots on
each piece.