Quadra-Fire • Expression 36 (QV36A-FB) • 2062-900 Rev. S • 11/11

12

O

N

P

R

Q

X

= AIR SUPPLY INLET

A

= 12 inches.................clearances above grade, veranda,

porch, deck or balcony

B =

12 inches.................clearance to window or door that may

be opened, or to permanently closed
window

C

= 18 inches.................clearance below unventilated soffi t

18 inches.................clearance below ventilated soffi t

30

inches ................clearance below vinyl soffits and

electrical service

D

= 6 inches...................clearance to outside corner

E

= 6 inches...................clearance to inside corner

F

= 3 ft. (Canada) ..........not to be installed above a gas me-

ter/regulator assembly within 3 feet
horizontally from the center-line of the
regulator

G =

3

ft

...........................clearance to gas service regulator

vent outlet

H =

12

inches.................clearance to non-mechanical (unpow-

ered) air supply inlet, combustion air
inlet or direct-vent termination

i

= 3 ft. (U.S.A.)

6 ft. (Canada) ...........clearance to a mechanical (powered)

air supply inlet

All mechanical air intakes within 10 feet of a termination cap

must be a minimum of 3 feet below termination.
J =

7

ft.

.........................

On

public property: clearance above

paved sidewalk or a paved driveway.

A vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings
and serves both dwellings.

V

= VENT TERMINAL

= AREA WHERE TERMINAL IS NOT PERMITTED

C

J

B

D

B

F

B

A

E

V

V

V

V

V

V

M

H or I

V

G

X

V

H

A

V

V

H

Electrical

Service

V

K

V

K

V

L

C

V

N

= 6 inches ........... non-vinyl sidewalls

12 inches ......... vinyl sidewalls

O =

18

inches ......... non-vinyl soffi t and overhang

42 inches ......... vinyl soffi t and overhang

P =

8

ft.

Q

MIN

R

MAX

1 cap

3 feet

2 x Q

ACTUAL

2 caps

6 feet

1 x Q

ACTUAL

3 caps

9 feet

2/3 x Q

ACTUAL

4 caps

12 feet

1/2 x Q

ACTUAL

Q

MIN

= # termination caps x 3 R

MAX

= (2 / # termination caps) x Q

ACTUAL

Covered Alcove Applications

(Spaces open only on one side and with an overhang)

Measure horizontal clearances from this surface.

Measure vertical clearances from this surface.

CAUTION! Risk of Burns! Termination caps are HOT,

consider proximity to doors, traffi c areas or where people
may

pass or gather (sidewalk, deck, patio, etc.)

. Listed cap

shields available. Contact your dealer.

• Local codes or regulations may require different

clearances.

• Vent system termination is NOT permitted in screened

porches.

• Vent system termination is permitted in porch areas with

two or more sides open.

• Hearth & Home Technologies assumes no responsibility

for the improper performance of the appliance when the
venting system does not meet these requirements.

• Vinyl protection kits are suggested for use with vinyl siding.

M =

18 inches ....................clearance under veranda, porch, deck,

balcony or overhang

42

inches ................vinyl or composite overhang

Permitted when veranda, porch, deck or balcony is fully open

on a minimum of 2 sides beneath the fl oor.

K

= 6 inches................. clearance from sides of electrical

service

L =

12

inches................

clearance above electrical service

Location of the vent termination must not interfere with access to the
electrical service.

Figure 4.4 Minimum Clearances for Termination