Quadra-Fire • Expression 36 (QV36A-FB) • 2062-900 Rev. S • 11/11

B. Disassembly of Vent Sections

To disassemble any two pieces of pipe, rotate either section
(see Figure 8.11), so that the seams on both pipe sections
are aligned (see Figure 8.12). They can then be carefully
pulled apart.

Securing the Vent Sections

Vertical Sections

Vertical sections of pipe must be supported every 8 feet
after the 25 foot maximum unsupported rise. The vent sup-
port or plumber’s strap (spaced 120° apart) may be used
to do this (see Figure 8.9).

Horizontal Sections

Horizontal sections of vent must be supported every 5 feet
with a vent support or plumber’s strap.

Figure 8.9 Securing Vertical Pipe Sections

Figure 8.12 Align and Disassemble Vent Sections

Figure 8.11 Rotate Seams for Disassembly

Figure 8.10 Securing Horizontal Pipe Sections

Improper support may allow vent to sag or separate.

Fire Risk.
Explosion Risk.
Combustion Fume Risk.

Use vent run supports per installation
instructions.

Connect vent sections per installation
instructions.

• Maintain all clearances to combustibles.
• Do NOT allow vent to sag below

connection point to appliance.

WARNING