Digital Solid State Soft Starters 18 – 1250A

3

1.1.3 Design

Specifications

Type of Load:

Three phase AC induction motors

AC Supply Voltage:

Universal, 208 - 600VAC ±10%, 50/60 Hz

Power Ratings:

18 - 1250 Amps, 7.5 - 1000 HP @ 460V

Unit Capacity - Continuous

Max. Amp rating is UL Listed continuous rating

Unit Capacity - Overload Rating
(Percent of motor FLA)

350% - 30 seconds

600% - 10 seconds

Power Circuit

6 SCRs, full phase angle firing using a hard fire picket firing circuit and “Back
Porch” DC carryover to avoid motor transient problems

SCR Firing Angle Detection

6 pulse Independent Locked Phase Tracking with Auto-synchronization,
prevents misfiring on unstable source frequency

SCR PIV Ratings
(Peak Inverse Voltage)

1600V

Phase Rotation

Operates with any phase sequence, or
programmable rotation trip ABC / ACB / Off

Transient Protection

RC snubber dv/dt networks on each phase

Cooling

Fan assisted convection

Bypass Contactor

Standard on all NEMA 12 enclosed units

Units 160A and less: Standard on all open panel units (-BP versions)

Units 210A and over:

Optional on open panel units (-BP versions)

Bypass Contactor Rating

Shunt rated or can be sized for Line start rated contactor (see charts)

Bypass Contactor Control

Integral control is included, but contactor can be externally controlled as well.

Ambient Condition Design

Open panel mount units: 0° to 50 °C (32° to 122°F)

Factory enclosed units: 0° to 40°C (32° to 104°F)

5 - 95% relative humidity

0 - 3300 ft. (1000m) above sea level without derating

Control Power

120VAC (customer supplied), 240VAC optional

Inputs

6 Dry (voltage free) contact inputs using 24VDC from an internal power supply

Programmable Outputs

3 relays, 2 each Form C (SPDT), 1 each Form A (SPST).
Can be programmed for 26 functions, with delays or flashing.

Output Relay Contact Rating 5 Amps, 240VAC max. (1200VA)

Dedicated Fault Output

AC Triac solid state switch

240VAC/DC, 50mA max.

Approvals

UL Listed, Canadian UL (cUL) Listed, CE Approved


Advertising