TE Series

Digital Solid State Soft Starters 18 – 1250A

32

5.5.7 Process Timer Features

5.5.8

Current and Ground Fault Protection Features

Fn # Group

Function Description

Adjustment / Display Range

Setting

Increments

Factory

Setting

Section

F030

Run Timer

a

nd Time Clock Co

n

troller

Mo

des

Run Timer Selection

0 = Disabled (No timer operation)
1 = Minimum (Batch) Run Timer
2 = Permissive Run Timer

1

0

Disabled

5.6.7

and

Append.

4

F031

Run Timer Time
for use in F030 above

1-9999 minutes after a Start
Command or Start Event from TCC

1 1

F032

24hr

Time Clock Controller (TCC)
Start Event Mode.

Chose “One Shot”
or 1 to 7 “Start Events”
from F033 – F039

Run time for this mode comes
from F030 above.

Start Event Cycle (SEC) Settings.

1 = Loop SEC every day
2 = Loop SEC every 2

nd

day

3 = Loop SEC every 3

rd

day

4 = Loop SEC every 4

th

day

5 = Loop SEC every 5

th

day

6 = Loop SEC every 6

th

day

7 = Loop SEC one day per week
8 = Single 24hr SEC

(until programmed again)

0 = One Shot: Start Event comes

from Start command only

1

0

One Shot

F033

Start Event #1 Start Time

00:00-23:59 (hh:mm) or OFF

1

OFF

F034

Start Event #2 Start Time

00:00-23:59 (hh:mm) or OFF

1

OFF

F035

Start Event #3 Start Time

00:00-23:59 (hh:mm) or OFF

1

OFF

F036

Start Event #4 Start Time

00:00-23:59 (hh:mm) or OFF

1

OFF

F037

Start Event #5 Start Time

00:00-23:59 (hh:mm) or OFF

1

OFF

F038

Start Event #6 Start Time

00:00-23:59 (hh:mm) or OFF

1

OFF

F039

Start Event #7 Start Time

00:00-23:59 (hh:mm) or OFF

1

OFF

Table 5.5.7: Run Timer and Time Clock Controller Function Group

Fn # Group

Function Description

Adjustment / Display Range

Setting

Increments

Factory

Setting

Section

F040

Current

an

d Gr

oun

d Fa

ult Pr

ot

ectio

n

Current Imbalance Trip

0 = Disabled, or
5 - 30% imbalance

1%

0

Disabled

5.6.8

F041

Current Imbalance Trip Delay

1 - 20 seconds

1 second

2

seconds

F042

Over Current Trip

0 = Disabled, or
100 - 300% of motor FLA

1%

0

Disabled

F043

Over Current Trip Delay

1 - 20 seconds

1 second

1 second

F044

Under Current Trip

0 = Disabled, or
10 - 90% of motor FLA

1%

0

Disabled

F045

Under Current Trip Delay

1 - 60 seconds

1 second

2

seconds

F046 Ground

Fault

Trip

0 = Disabled, or
5 - 90% of CT ratio from Fn 74

1%

0

Disabled

F047

Ground Fault Trip Delay

1 - 60 seconds

1 second

2

seconds

Table 5.5.8: Current and Ground Protection Features Group