TE Series

Digital Solid State Soft Starters 18 – 1250A

79

F033 = Event #1 Start Time

Factory Setting = OFF
Range = 00:00 through 23:59, or OFF
This function is used to select the start time for Event #1 in the
TCC above. Once given a Start command after this event time,
the starter will run the motor according to the selections entered
into F030 and for the time entered into F031.

F034 = Event #2 Start Time Same as above, except for event #2

F035 = Event #3 Start Time Same as above, except for event #3

F036 = Event #4 Start Time Same as above, except for event #4

F037 = Event #5 Start Time Same as above, except for event #5

F038 = Event #6 Start Time Same as above, except for event #6

F039 = Event #7 Start Time Same as above, except for event #7
ƒ NOTE:

Start Events are completely independent of one another, and can
be programmed in any order. For instance, the Start Time in F037
can be earlier than the Start Time in F033. This allows easier
alterations or additions of new Start Times after a unit is already
installed.