Toshiba 18 - 1250 A User Manual

Page 20

Advertising
background image

TE Series

Digital Solid State Soft Starters 18 – 1250A

13

ƒ 3.1.3.c

Overload Protection During Bypass

When an integral Bypass Contactor is used to shunt power around
the SCRs in the TE Series (as in the TE…-BP version), overload
protection is maintained as long as the TE Series is directly
controlling the contactor. No additional Overload Relay is
necessary for normal operation.

CAUTION

If a Bypass Contactor is added by the user in the field (i.e. 210A units and above), care
must be taken to ensure proper power routing to ensure functioning of the Overload
protection. Consult factory for assistance.

ƒ When the Bypass Contactor on a TE…-BP Series has been

selected to be used for Across-the-Line restart (reference section
1.2.3), supplemental overload protection may be necessary. For this
application, refer to the External Overload Relay Applications
supplement and wiring diagram in Appendix 5 and section 4.2.6.a.

ƒ 3.1.3.d

Dynamic Reset Capacity

The TE Series includes the ability to dynamically track the Thermal
Capacity needed for a successful restart after an overload trip. It
averages the Thermal Capacity consumed in the previous three
successful starts, and calculates a Thermal Capacity to Start
(viewed in Function F059). After tripping on Overload, the Thermal
Register must have regained the amount recorded in F059 before a
Reset will be allowed. If the display reads [ Inh] when attempting to
reset an overload trip, it is indicating that the starter is Inhibited from
being reset.

Refer to details of Function F071 for information on emergency
override of lockouts such as this.

3.2

NEMA Class Trip Curves

NEMA Class trip curves are based on a common tripping point of 600%
of motor Full Load Amps (FLA). Curves vary by the amount of time
before the unit trips. As an example, a Class 20 curve will trip in 20
seconds at 600% of FLA. The factory default setting of Class 10 will trip
in 10 seconds at 600% of FLA.

3.2.1 Dual Overload Trip Curves

The TE Series Soft Starter provides two separate Overload Trip
Protection Curves, one for starting and one for running conditions. The
starter’s At-Speed detection circuit determines when the motor has
reached full speed. When the At-Speed condition is reached, the
overload trip curve will shift from the Start to the Run level, as
programmed in Functions F003 and F004. See Section 5.6.1 for
programming details.

3.2.2 Starting Overload Trip Curve

During the start mode, Overload Trip Curves are selectable from NEMA
Class 5 through Class 20 only. The default setting of Class 10 allows
protection for the overload capacity of the soft starter as well as the
motor. Use a higher Trip Class only if nuisance tripping occurs with the
default setting.

Advertising