TE Series

Digital Solid State Soft Starters 18 – 1250A

31

5.5.3

Jog Mode Functions

5.5.4

Kick Start Mode Functions

5.5.5 Decel Mode Functions

5.5.6 Restart Function

Fn # Group

Function Description

Adjustment / Display Range

Setting

Increments

Factory

Setting

Section

F019

Jog M

odes

Voltage Jog

5 – 100% Line Voltage

1%

50%

5.6.3

and

4.2.5.b

F020

Time of Voltage Jog

1 – 20 Seconds

1 second

10

seconds

F021

Current Jog

100 – 500% Motor

Current 1%

150%

Table 5.5.3: Jog Mode Function Group

Fn # Group

Function Description

Adjustment / Display Range

Setting

Increments

Factory

Setting

Section

F022

Kick Mo

de

Kick Start Voltage

0 = Disabled, or
10 - 100% Line Voltage

1%

0

Disabled

5.6.4

F023

Kick Start Time

0.1 - 2 Seconds

0.1second

0.8

seconds

Table 5.5.4: Kick Start Mode Function Group

Fn # Group

Function Description

Adjustment / Display Range

Setting

Increments

Factory

Setting

Section

F024

Pump Flex Dec

e

l

Mode

Pump Flex Control /
Deceleration Ramp

0 = Disabled (coast to stop)
1 = Enabled, except after OL trip
2 = Enabled, continued Decel even

if there is an OL trip

1

0

Disabled

5.6.5

and

Append.

2

F025

Begin Decel Level (BDL),
Immediate Drop Down Torque

0 - 100 % of Output Voltage

1%

60%

F026

Decel Shut Off Voltage

0 to (BDL minus 1)% Voltage

1%

30%

F027

Decel Ramp Time

1 – 60 Seconds

1 second

10

seconds

Table 5.5.5: Pump Flex Decel Mode Function Group

Fn # Group

Function Description

Adjustment / Display Range

Setting

Increments

Factory

Setting

Section

F028

Restart

Restart Delay Time
(Sequential Start Delay)

0 = Disabled, or
1-999 seconds after a Power Loss
(Status can be read in F054)

1 second

0

Disabled

5.6.6

F029

Reserved for Factory Use

Table 5.5.6: Restart Function Group